NA-9188 

1. NA-9188 Specification 

* Specifications and designs could be changed without advance Notice. 

Class 2, adjacent to voltage rating (30Vmax.) 

ITEM 

SPECIFICATION 

ITEM 

SPECIFICATION 

Ambient Temp. 

-20℃~55℃ / -40℃~85℃ 

Network Type 

EtherNet/IP, BOOTP 

Relative Humidity 

5% ~ 90% without condensation 

Cable 

EtherNet Cable 

Durable-vib./impact 

IEC68-2-6(2G) / 10G 

Cable Length(m) 

Up to 100m from Ethernet Hub 

EMC/ESD 

EN50082 / EN50081 

Comm. Sp(Kbps) 

10/100Mbps 

Mount Position 

On the left of FnIO-S series 

Expansion No. 

Max. 32 module 

Atmosphere 

Not so dusty without corrosive gas 

Max. node 

Limited by Ethernet Specification 

Field Supp.Volt. 

Class 2, 24VDC 

24VDC (11VDC ~ 28.8VDC)

 

Max. Digital I/O 

Input : 2016points/Output : 

2016points 

Field Supp. Cur. 

Max. 10A 

Max. Analog I/O 

Input : 126Ch / Output : 126Ch 

FnBus Sup. Cur 

Max. 1.5A@5Vdc 

Max. Byte size 

Input : 252Bytes / Output : 252Bytes 

Isolation 

System power to internal logic :  

Non-isolation  

System power to I/O driver : 

Isolation 

Operating Mode 

Ethernet/IP, BOOTP 

Size 

45mm 

×

 99mm 

×

 70mm 

IP Address Setting 

BOOTP 

Weight 

150g 

Power Dissipation 

60mA typical @24Vdc 

Certification 

UL / cUL / CE / FCC / RoHS(EU, 

China) 

   

   

Cautions for your Safety 

Do not assemble the products and wire with power applied to the system. Else it may cause an electric arc, which can result into unexpected 
and potentially dangerous action by field devices. Arching is explosion risk in hazardous locations. Be sure that the area is non-hazardous or 
remove system power appropriately before assembling or wiring the modules. 

Do not touch any terminal blocks or IO modules when system is running. Else it may cause the unit to an electric shock or malfunction. 

Keep away from the strange metallic materials not related to the unit and wiring works should be controlled by the electric expert engineer. 
Else it may cause the unit to a fire, electric shock or malfunction. 

If you don’t follow the directions, it could cause a personal injury, damage to the equipment or explosion 

If you disobey the instructions, there may be possibility of personal injury, damage to equipment or  
explosion. Please follow below Instructions. 

   Check the rated voltage and terminal array before wiring. Avoid the circumstances over 55

 of temperature. Avoid placing it directly in the  

      sunlight.  

   Avoid the place under circumstances over 85% of humidity.  

   Do not place Modules near by the inflammable material. Else it may cause a fire. 

   Do not permit any vibration approaching it directly.  

   Go through module specification carefully, ensure inputs, output connections are made with the specifications. Use standard cables for wiring.  

   Use Product under pollution degree 2 environment. 

Before using the unit                                                                        

*We appreciate you for purchasing CREVIS Products. To use the units more effectively, please read this quick guide and refer to 
the respective user manual for further details. 

Warning

Caution! 

* Power Isolators must be used according to the usage of 5VDC/24VDC/48VDC or AC Voltage modules 

Summary of Contents for FnIO S Series NA-9188

Page 1: ...ries Max 32 module Max Nodes Limited by Ethernet Specification Class 2 24VDC 24VDC 11VDC 28 8VDC Operating Mode Ethernet IP BOOTP 10A Digital I O Input 2016 Output 2016 FnBus 1 5A 5Vdc Analog I O Inpu...

Page 2: ...2 5 System Field 1 Field 1 Serial System 2 Field I O 2 Power Supply Field Power Supply 3 Tape 4 Serial 5 System I O 3 3 1 Din Rail 3 2 Din Rail Din rail Din Rail 2 1 EtherNet Communication Line wirin...

Page 3: ...s already in use Configure the module with a unique IP address LINK Link Active Status LED Off Not Powered Physical network not ready May not be powered Green Link Operational Physical Network communi...

Page 4: ...5 I O Image Mapping 6 Hub FnIO FnIO 100m 100m I O Data Configuration Data Memory Resister 3 Data Network Adapter Data EIP HUB 29 4 031 899 4599 FAX 031 899 4509 www crevis co kr...

Page 5: ...entially dangerous action by field devices Arching is explosion risk in hazardous locations Be sure that the area is non hazardous or remove system power appropriately before assembling or wiring the...

Page 6: ...cated mount Pull up the module to remove from the din rail Notice for Wiring of communication and Field power 1 The communication power and Field power respectively are supplied to each network adapte...

Page 7: ...One or more of the connections in which the module is The target has time out Red Duplicate IP Address Module has detected that its IP address is already in use Configure the module with a unique IP a...

Page 8: ...Resister Network Adapter has memory field for In Output data respectively Specifications and designs may be changed without advance Notice Caution Industrial HUB for EIP recommended Cable the noise c...

Reviews: