FieldBus Input/Output System 

 

PROFINET Network Adapter 

 PROFIBUS  Network Adapter 

 Digital Input / Output 

 Analog  Input / Output 

 Special Module 

Quick Guide 

FnIO S-series 

NA-9187 

1. NA-9187 Specification 

Before using the unit  

We appreciate your purchasing CREVIS products. To use the units more effectively, please read this manual first. 

ITEM 

SPECIFICATION 

ITEM 

SPECIFICATION 

Surrounding Air 

Temp./  

Ambient Temp. 

-20℃~55℃ / -40℃~85℃ 

Network Type 

PROFINET I/O RT 

Relative Humidity 

5% ~ 90% without condensation 

Cable 

Ethernet Cable 

Durable-vib./impact 

IEC68-2-6(2G) / 10G 

Cable Length(m) 

Up to 100m from Ethernet Hub 

EMC/ESD 

EN50082 / EN50081 

Comm. Sp(Kbps) 

10/100Mbps 

Mount Position 

On the left of FnIO-S series 

Expansion No. 

Max. 32 module 

Atmosphere 

Not so dusty without corrosive gas 

Max. node 

Limited by the IP address 

Field Supp.Volt. 

Class 2, 24VDC 

24VDC (11VDC ~ 28.8VDC)

 

Max. Digital I/O  Input : 2016point / Output : 2016point 

Field Supp. Cur. 

Max. 10A 

Max. Analog I/O 

Input : 126Ch / Output : 126Ch 

FnBus Sup. Cur 

Max. 1.5A@5Vdc 

Max. Byte size 

Input : 252Bytes / Output : 252Bytes 

Isolation 

System power to internal logic :  

Non-isolation  

System power to I/O driver :  

Isolation 

Topology 

Line or Star topology 

Size 

45mm 

×

 99mm 

×

 70mm 

Node No. Setting 

Rotary Switch 2ea(x10, x1) 

Weight 

150g 

Power Dissipation 

115mA typical @24Vdc 

Certification 

UL / cUL / CE / FCC / RoHS(EU, 

China) / PROFINET 

   

   

Cautions for your Safety 

Do not assemble the products and wire with power applied to the system. Else it may cause an electric arc, which can result into unexpected 
and potentially dangerous action by field devices. Arching is explosion risk in hazardous locations. Be sure that the area is non-hazardous or 
remove system power appropriately before assembling or wiring the modules. 

Do not touch any terminal blocks or IO modules when system is running. Else it may cause the unit to an electric shock or malfunction. 

Keep away from the strange metallic materials not related to the unit and wiring works should be controlled by the electric expert engineer. 
Else it may cause the unit to a fire, electric shock or malfunction. 

If you don’t follow the directions, it could cause a personal injury, damage to the equipment or explosion 

If you disobey the instructions, there may be possibility of personal injury, damage to equipment or  
explosion. Please follow below Instructions. 

   Check the rated voltage and terminal array before wiring. Avoid the circumstances over 55

 of temperature. Avoid placing it directly in the  

      sunlight.  

   Avoid the place under circumstances over 85% of humidity.  

   Do not place Modules near by the inflammable material. Else it may cause a fire. 

   Do not permit any vibration approaching it directly.  

   Go through module specification carefully, ensure inputs, output connections are made with the specifications. Use standard cables for wiring.  

   Use Product under pollution degree 2 environment. 

Warning

Caution! 

Class 2, adjacent to voltage rating (30Vmax.) 

* Power Isolators must be used according to the usage of 5VDC/24VDC/48VDC or AC Voltage modules 

* Specifications and designs could be changed without advance Notice 

Summary of Contents for FnIO S Series NA-9187

Page 1: ...es Max 32 module Max Nodes Limited by the IP address Class 2 24VDC 24VDC 11VDC 28 8VDC Topology Line or Star topology 10A Digital I O Input 2016 Output 2016 FnBus 1 5A 5Vdc Analog I O Input 126Ch Outp...

Page 2: ...e Value Description Factory settings 0 flash NA9187 1 IP flash Name of station NA9187 IP address 192 168 0 100 Subnet mask 255 255 255 0 Gateway 192 168 0 1 1 99 NA9187 xx xx Rotary Switch Node No IP...

Page 3: ...n NET LED Off IO OFF OFF Flashing Red 0 1s Flashing Green 0 1s Parameters PROFINET IO Parameter Red PROFINET IO Flashing Red 0 5s PROFINET IO Flashing Green 0 5s PROFINET IO Green PROFINET IO IO LED O...

Page 4: ...MEMO 446 930 29 4 TEL 031 899 4599 FAX 031 899 4509 Homepage www crevis co kr...

Page 5: ...it may cause an electric arc which can result into unexpected and potentially dangerous action by field devices Arching is explosion risk in hazardous locations Be sure that the area is non hazardous...

Page 6: ...8 0 1 1 99 Name of station will be NA9187 xx xx is the value of Rotary Switch IP address will be read from flash memory Notice for MAC ID Station No Setting 1 Set within the range of connectible Node...

Page 7: ...ata exchange has taken place Flashing Red 0 5s PROFINET IO connection is aborted before a data exchange has taken place Flashing Green 0 5s PROFINET IO Data Exchange stop Green PROFINET IO Data Exchan...

Page 8: ...Specifications and designs may be changed without advance Notice Crevis Co Ltd 29 4 Gigok ro Giheung gu Yongin si Gyeonggi do Korea 446 930 TEL 82 31 899 4599 FAX 82 31 899 4509 Homepage www crevis c...

Reviews: