“Troubleshooting Communications” section in the respective Operations
Guide for the control system.
There are two different methods—Method A or Method B—for setting
the Net ID:
Method A
(Cresnet address-settable ID), described below, applies to
devices in a Cresnet system with a CNX control system or with a 2-
Series control system and requires that a single unit be the only network
device connected to the control system.
Method B
(Touch Settable ID or TSID), which begins on page 20,
applies to all TSID-ready devices in a Cresnet system with 2-Series
control system upgrade file (CUZ) version 3.029 or later. TSID
functionality makes it possible for the control system to recognize a
network device via its serial number, which is stored in the device’s
memory. This method does not require that any devices be disconnected
from the network; Net IDs may be set with the entire Cresnet system
intact. This method requires the use of the Crestron Viewport version
3.35 or later.
Use the appropriate method to set the Net ID.
Method A (Cresnet address-settable ID)
1. Ensure that the device requiring a Net ID change is the only
unit connected to the control system.
2. Open the Crestron Viewport.
3. From the Viewport menu, select
Functions | Set Network ID
.
The software checks the baud rate and then opens the "Set
Network ID" window.
4. In the "Set Network ID" window, select the device requiring a
Net ID change from the
Current Network Devices
text
window.
5. Select the new Net ID for the device from the
Choose the new
network ID for the selected device (Hex):
text box.
6. Click
Set ID
to initiate the change. This will display the "ID
command has been sent" window.
7. In the "Command Complete" window, click
OK
.
Operations & Installation Guide - DOC. 6237A
Wall Plate Media Center: QM-WMC
•