Product Manual — Doc. 9212A
PC-350V-12 and PC-350V-18 • 12
Specifications
This section provides the following information:
l
Technical Specifications (below)
l
Dimension Drawings (on page 15)
Technical Specifications
Power Conditioner
Maximum Output
Current, Total:
12A @ 120VAC
Maximum Output
Current, Per Outlet:
12A @ 120VAC (subject to a maximum total output current of 12A for all outlets
combined)
Filtration for the
FILTERED outlets:
-1.9 dB @ 100 kHz, -25 dB @ 300 kHz, -39 dB @ 500 kHz with 50 Ohm load
Surge Protection Modes:
Line-Ground, Line-Neutral, Neutral-Ground
Surge Protection
Shutoff:
Shuts off outlets if surge protection is compromised
Joule Rating:
3640 Joules
Clamping Voltage:
600V
Clamping Time:
1 ns
Wiring Fault Detection:
Shuts off outlets if the following wiring faults are detected at the input:
l
Reversed polarity
l
Missing ground wire
Voltage Sensing Range:
90 to 145V rms ±1%, measured at input
Current Sensing Range:
0.1 to 12A rms ±1% when load > 1A, measured per outlet
Under Voltage Cutoff:
Adjustable 90 to 100V, shuts off outlets if input drops below set value
Over Voltage Cutoff:
Adjustable 130 to 145V, shuts off outlets if input exceeds set value
Cycle Delay Adjustment:
5 to 300 seconds, adjustable per outlet
Startup Delay
Adjustment:
1 to 10 seconds, adjustable per outlet
Power
Line Power
12A @ 120VAC, 60 Hz
Summary of Contents for PC-350V Series
Page 1: ...PC 350V Series Power Controllers Product Manual Crestron Electronics Inc...
Page 5: ...v Contents Product Manual Doc 9212A...
Page 15: ...15 PC 350V 12 and PC 350V 18 Product Manual Doc 9212A Dimension Drawings PC 350V 12 PC 350V 18...
Page 68: ...This page is intentionally left blank Product Manual Doc 9212A PC 350V 12 and PC 350V 18 68...