infiNET™ Switches 

Crestron 

CLW-SW1/4RF, -SWS1/4RF, -SLVS1RF

 

infiNET Gateway and, if more devices are needed, more C2N-MNETGW gateways 
may be added to a Cresnet

®

 network. 

Crestron infiNET switches operate on the 2.4 GHz “ISM band” (2400 MHz to 
2483.6 MHz) at 10 mW. The output power of these devices allow RF signals to 
travel approximately 150 feet indoors and 250 feet outdoors (subject to site-specific 
conditions) without the use of repeaters or other infiNET devices. The range is 
dependent on construction of the building, obstructions, and RF interference from 
other devices. The location of the dimmer is an important factor in determining RF 
performance. Adding more infiNET devices or repeaters to the network effectively 
increases the range, strength, and reliability of the network.  

The -SW1RF and -SW4RF feature a three-position mode selection switch. Refer to 
“Operation” on page for more information. In the absence of control system 
communications, the switch can still be used to control the attached load. 

The CLW-SWS1RF (-SWS1RF) and CLW-SWS4RF (-SWS4RF) are similar to the  
-SW1RF and -SW4RF (respectively) with the added capability of working with one 
or more slave units (CLW-SLVS1RF) in a multi-switch / single circuit application. 
For more information, refer to the latest version of the infiNET Switches Installation 
Guide (Doc. 6293) which is available from the Crestron website 
(www.crestron.com/manuals). 

The CLW-SLVS1RF (-SLVS1RF) is a slave unit that when used in conjunction with 
the -SWS1RF or -SWS4RF acts as an additional switch control point in a multi-
switch / single circuit application. It does not connect to an infiNET system and 
cannot be used without a -SWS1RF or -SWS4RF. The -SLVS1RF does not have a 
mode selection switch. It can only be programmed when used in conjunction with a  
-SWS4RF (refer to “Attaching and Detaching the Electrical Load” on page 27). 
Otherwise, it will emulate the 

RUN

 mode of the -SWS1RF (even if connected to a  

-SWS4RF) unless the mode selection switch of the master is set to “OFF”.  

These switches can be ordered with custom engraved buttons already installed by 
Crestron. Engraved buttons cannot be installed or changed in the field. Contact 
Crestron for more information. 

These switches are available in white, almond, and black. White units are designated 
by part numbers ending in “W”. Almond units are designated by part numbers 
ending in “A”. Black units are designated by part numbers ending in “B”. Each 
dimmer can be covered with a decorative faceplate (not supplied). 

For installation instructions, refer to the latest version of the infiNET Switches 
Installation Guide (Doc. 6293), which is available from the Crestron website. 

Specifications 

Following are specifications for the -SW1RF, -SW4RF, -SWS1RF, -SWS4RF, and  
-SLVS1RF. 

CLW-SW1/4RF, CLW-SWS1/4RF, & CLW-SLVS1RF Specifications 

SPECIFICATION DETAILS 

Power Requirements 

Line Power, 120 VAC, 60 Hz 

Operating Frequency 

2400 MHz to 2483.6 MHz  
(802.15.4 compliant) 

RF Output Power 

10 mW 

(continued on following page) 

2  

  infiNET Switches:  Crestron CLW-SW1/4RF, -SWS1/4RF, -SLVS1RF 

Operations Guide - DOC. 6397 

Summary of Contents for CLW-SW1

Page 1: ...Crestron CLW SW1 4RF CLW SWS1 4RF CLW SLVS1RF infiNET Switches Operations Guide...

Page 2: ...ctronics Inc 15 Volvo Drive Rockleigh NJ 07647 1 888 CRESTRON All brand names product names and trademarks are the property of their respective owners Windows and Windows XP are registered trademarks...

Page 3: ...de 12 Using Touch Settable ID TSID to Set MNET ID 12 Manually Setting the MNET ID in Crestron Toolbox 19 Programming Software 21 Earliest Version Software Requirements for the PC 22 Programming with D...

Page 4: ......

Page 5: ...d interference One button and four button configurations available in white black and almond Can be ordered with custom engraved buttons Can operate as a local load control or infiNET keypad These swi...

Page 6: ...s a slave unit that when used in conjunction with the SWS1RF or SWS4RF acts as an additional switch control point in a multi switch single circuit application It does not connect to an infiNET system...

Page 7: ...A SWS1RF SWS4RF 3A SLVS1RF N A Minimum Load 40W 0 5A Operating Temperature and Humidity 32 F to 104 F 0 C to 40 C 10 to 90 Relative Humidity Non Condensing SW1RF SW4RF and SWS1RF SWS4RF Height 4 13 in...

Page 8: ...Physical Description The SW1RF and SWS1RF have a light emitting diode LED with adjustable brightness via Crestron programming software a rocker button and a three position mode selection switch as sho...

Page 9: ...s via Crestron programming software four pushbuttons and a three position mode selection switch as shown in the following diagrams Each of the buttons may be pushed to perform certain functions The fu...

Page 10: ...8 32 cm 3 81 in 9 68 cm 4 13 in 10 48 cm 1 88 in 4 77 cm 2 70 in 6 86 cm 1 50 in 3 81 cm The SLVS1RF is similar in appearance to the SW1RF and SWS1RF but does not have the three position mode selectio...

Page 11: ...5 19 This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interfer...

Page 12: ...tiple gateways are installed only one gateway should be in the Acquire mode at a time 2 Place the SW1RF SW4RF SWS1RF SWS4RF into the Acquire mode by doing the following a Move the mode selection switc...

Page 13: ...ess and hold the top or bottom of the button on the SW1RF SWS1RF or any button on the SW4RF SWS4RF 3 While holding the button slide the mode selection switch to the RUN position 4 Hold the button for...

Page 14: ...tap Button 1 1 If delay is set to 0 seconds the load will turn off immediately 2 If the switch was in the middle of a delay pressing the button will cancel the delay and turn off the load immediately...

Page 15: ...ce the LED can be in one of three intensity levels OFF LOW and HIGH The following table describes the LED pattern in all modes of operation Dimmer Operation LED Behavior LED BEHAVIOR DEVICE STATE LOW...

Page 16: ...change device MNET IDs for any device on the infiNET network MNET IDs can be set with the touch settable ID TSID function or manually To use TSID to set MNET IDs continue reading Using Touch Settable...

Page 17: ...MNET ID 01 as shown in the Network Device Tree window below Network Device Tree 1 With the Network Device Tree open select Tools SMW Program Tree or click SMW Program Tree Click to Select Program 2 C...

Page 18: ...riptions such as BR Dimmer LR Dimmer and kitchen switch were created by editing each devices symbol name in the SIMPL Windows Programming Manager For information on editing a symbol name refer to the...

Page 19: ...ee to the Network Device Tree Link Instruction Window 5 Click OK The cursor will change to a target selector 6 Click on the Network Device tree that is to be linked to the SMW Program Tree A message w...

Page 20: ...me an installer may want to first identify a device by the entryway then a device in the hallway followed by devices in a room Devices that do not need to be identified can be removed from the list by...

Page 21: ...l be highlighted Touching a device may result in setting a duplicate MNET ID A warning will be displayed Duplicate MNET ID Warning Click Yes to set the device to the duplicate MNET ID the status will...

Page 22: ...When all devices have been identified a summary will be displayed in the upper portion of the window Setup Complete 11 Click Close to close the window once all devices have been identified All of the...

Page 23: ...gram use the Touch Settable ID method described on page 12 to change the MNET ID to match the MNET ID specified in the SIMPL Windows program NOTE You may also use D3 Pro or SystemBuilder to perform MN...

Page 24: ...en the sub menu appears select Change Network ID Network Device Tree Sub Menu NOTE Any infiNET switch in the Network Device Tree can be identified using Crestron Toolbox Right click a device in the Ne...

Page 25: ...ired While traditional programming tools can still be used to program a system D3 Pro and SystemBuilder can be used to easily complete all necessary programming for a base system including all touchpa...

Page 26: ...r o Crestron Engraver 2 2 2 3 or later o CUZ 3 154 for 2 Series processors or later Optional SystemBuilder version 2 0 or later with SystemBuilder Templates version 2 0 1or later Also requires o Visio...

Page 27: ...which a programmer can select configure program test and monitor a Crestron control system SIMPL Windows offers drag and drop functionality in a familiar Windows environment This section describes a s...

Page 28: ...er pane of System Views Additional units are assigned different Net ID numbers as they are added For more information on the Net ID of a C2N MNETGW refer to the latest revision of the C2N MNETGW Opera...

Page 29: ...adds the selected infiNET device with a default MNET ID Following are the default MNET IDs used by SIMPL Windows for each of the switch models CLW SW1RF 07 CLW SW4RF 09 CLW SWS1RF 08 CLW SWS4RF 0A NOT...

Page 30: ...atically changes MNET ID values of a device added to a program if a duplicate device or a device with the same default MNET ID already exists in the program Always ensure that the hardware and softwar...

Page 31: ...n be programmed in SIMPL Windows to control the electrical load or to perform another function in the control system program NOTE If a detached device restarts from either a power failure or from movi...

Page 32: ...ade via the Crestron Toolbox The following sections define how one would upload a SIMPL Windows program to the control system and upgrade the firmware of CLW SW1RF SWS1RF SW4RF SWS4RF However before a...

Page 33: ...re should match the protocol that the control system expects The usual settings are as follows Port COM 1 through COM 8 Select the correct COM port on the PC Baud rate Auto detect Parity None Number o...

Page 34: ...vice expand the network device tree by clicking Expand the network device tree until the device to be managed is selected Right click the desired MNET ID to open the sub menu This menu provides a wide...

Page 35: ...ower and the C2N MNETGW is connected to the control system 2 Reacquire the infiNET device on the C2N MNETGW Refer to Acquiring the Switch on the infiNET Network on page 8 for more information Also ref...

Page 36: ...you are connected to the control system the Functions option becomes available from the menu bar 4 Select Functions SIMPL Program The SIMPL Program window contains information about the currently load...

Page 37: ...Switches 5 Click the button to browse for a new compiled spz program Open Window 6 Select a file and click Open When the SIMPL Program window re opens click Send Operations Guide DOC 6397 infiNET Swit...

Page 38: ...firmware complete the following steps 1 Verify that the procedure for Establishing Communications that begins on page 28 has been performed 2 Open Crestron Toolbox and open the Network Device Tree the...

Page 39: ...dow 7 Click Open to select the file 8 The Firmware window reopens indicating the target device the new firmware version and release notes information Click View to view the release notes or click Send...

Page 40: ...cquire the device on infiNET network as described in Acquiring the Switch on the infiNET Network on page 8 If the LED flashes OFF for second two times then returns to low the MNET ID of device is not...

Page 41: ...of the SIMPL Windows program set the signal Enable_Local_Btn_Outputs high Switch does not operate as described in the manual Switch is detached from the load In the switch symbol of the SIMPL Windows...

Page 42: ...dvantage of Crestron s award winning customer service team by calling the Crestron corporate headquarters at 1 888 CRESTRON 1 888 273 7876 For assistance in your local time zone refer to the Crestron...

Page 43: ...mps are not covered This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regarding the nature and extent of the d...

Page 44: ...Crestron Electronics Inc Operations Guide DOC 6397 15 Volvo Drive Rockleigh NJ 07647 2014134 Tel 888 CRESTRON 12 05 Fax 201 767 7576 Specifications subject to www crestron com change without notice...

Reviews: