Crestron CLW-SLVS User Manual Download Page 5

 

CLW-SW, SWS, & SLVS(W/A/B)

 

7.  Attach decorative faceplate. 

NOTE:

  The RED (Load) and BLACK (Hot) wires are 

#14 AWG. The BLUE (Slave) and WHITE (Neutral) 
wires are #18 AWG. The GREEN (Ground) wire is #16 
AWG. The GRAY (Cresnet) wires are #22 AWG. The 
BLACK wire (Cresnet ground) paired with the GRAY 
(Cresnet) wires is #22 AWG. 

8. Restore 

power. 

Operating Buttons and Switches  

The -SW, -SWS, and -SLVS feature two pushbuttons (one 
large, and one small). The -SW and -SWS also have a 
three-position mode selection switch. The function of 
each button is determined by the position of the mode 
selection switch. Refer to the diagram below for the 
location of the buttons and the switch. 

CLW-SWS with CLW-SLVS Wiring 

NOTE:

 The -SWS must be installed in the same wallbox 

that contains the connections to the load. 

Buttons of CLW-SW, -SWS, and -SLVS 

The following wiring diagram illustrates installation of 
the -SWS with a -SLVS. 

Large Button

Small Button

Mode Selection Switch
(-SW & -SWS Only)

 

Wiring Diagram of CLW-SWS with CLW-SLVS 

Hot

Neutral

Load

RED

CLW-SWS

BLACK

WHITE

CLW-SLVS

BLUE

BLACK

BLUE

Ground

Ground

GREEN

GREEN

LINE

120VAC

60Hz

WHITE

Ground

GREEN

BLACK

BLUE

CLW-SLVS

WHITE

Cresnet

 

NOTE:

  Do not connect the BLUE (Slave) wire to the 

BLACK (Hot) or RED (Load) wires. 

NOTE:

  The -SLVS does not have a mode selection 

switch. It will act in the same mode as the -SWS. 

NOTE:

  The RED (Load) and BLACK (Hot) wires are 

#14 AWG. The BLUE (Slave) and WHITE (Neutral) 
wires are #18 AWG. The GREEN (Ground) wire is #16 
AWG. The GRAY (Cresnet) wires are #22 AWG. The 
BLACK wire (Cresnet ground) paired with the GRAY 
(Cresnet) wires is #22 AWG. 

OFF 

When the mode selection switch is in the “OFF” position, 
the buttons will not have any function and the load is 
disconnected from the power source. This 

must

 be used 

when changing light bulbs to ensure that the load is fully 
disconnected from power. 

NOTE:

  If a -SWS is installed without a -SLVS, the 

BLUE lead (Slave) should be capped. 

ADJ 

NOTE:

  The WHITE (Neutral) connection on the -SLVS 

is optional and is only required for operation of the LED. 
If the neutral is not available, the white lead should be 
capped off. 

When the switch is in the ADJ position, the load can be 
manually activated and deactivated by pressing the large 
button. Pressing and holding the small button will set a 
delay time for deactivating the load when the switch is in 
the PRE position. To set the delay time, press and hold 
the small button for the desired amount of time delay and 
release the button. When the small button is released, the 
LED will flash three times to confirm the time delay 
setting. When done, return the switch to the PRE position. 

5.  Splice the gray wires of the -SW or -SWS to the 

Class 2 low voltage wires connected to the 
Crestron control system, a Crestron power 
supply, or a Crestron connection block device. 
Push the wires and the splices into a hole in the 
drywall to provide the necessary separation. 

NOTE:  

If a time delay is not set, the factory default is 10 

seconds.

 

6.  Push all Class 1 Power wires back into the 

wallbox and fasten the device to the wallbox 
with the provided screws. 

Installation Guide – DOC. 6134B 

Stand Alone Wall Box Switch:  CLW-SW, SWS, & SLVS  

  5  

 