iLux Expansion Module
CLS-EXP-DIM
Installation Guide – DOC. 6638E
iLux Expansion Module: CLS-EXP-DIM
•
5
Connectors, Controls, and Indicators (Continued)
#
CONNECTORS,
CONTROLS, AND
INDICATORS
DESCRIPTION
6
OUTPUT–DIM OUT (1) Captive screw terminal,
dimmed load output
7
OUTPUT–HOT
(1) Captive screw terminal, line
power input
8
OUTPUT–NEUT
(1) Captive screw terminal,
neutral connection for line
power input and load
9
GROUND
(1) 3-terminal chassis ground
bus bar
1.
Captive screw terminals accept up to two 22 to 12 AWG (0.34 to
4.0 mm
2
) wires per terminal.
2.
CLW-Series device must have a dedicated neutral.
Setup
Important Notes
Read before installation.
•
Codes: Install in accordance with all local and
national electrical codes.
•
Wiring: Use 75°C copper wire only.
Installation
The CLS-EXP-DIM can be installed vertically on a wall
and can also be installed in a space used for
environmental air as defined in NEC Article 300.22(C).
Refer to the following diagram when installing a
CLS-EXP-DIM module.
Module Installation
Mounting Surface
CLS-EXP-DIM Module
Mounting Screw,
#8, Qty. 4 Total
(Not Supplied)
Ensure proper ventilation:
•
Install device vertically on a vertical surface.
NOTE
: To prevent potential heat damage to
drywall, do not mount the CLS-EXP-DIM directly
onto drywall. Mount a piece of 1/2 in (minimum)
thick plywood between the CLS-EXP-DIM and the
drywall.
•
Install device with 6 in (152 mm) of clearance from
the top and bottom of the device.
Hardware Hookup
WARNING
:
RISK OF SERIOUS PERSONAL
INJURY.
Turn off power at the circuit breaker(s) prior to
installation. Installing with power on can result in serious
personal injury and damage to the device.
1.
Use a #2 Philips screwdriver to remove the cover
screws as shown in the following diagram and
remove the cover.
Remove Cover Screws
Cover Screws
(x4)
2.
Depending on the module’s application, select the
appropriate configuration from one of the wiring
diagrams that follow and connect the CLS-C6. The
following wiring guidelines should be considered
when wiring the device:
•
Strip wires to 7/16 in (11 mm).
•
Tighten terminal screws to 7 in-lbs (0.79 Nm).
NOTE
: Dimmers controlling one or more
CLS-EXP-DIM modules must not be wired to
control any other type of load.