Crestron CLS-EXP-DIM Specfications Download Page 4

CLS-EXP-DIM

 

iLux Expansion Module

 

 

4  

  iLux Expansion Module:  CLS-EXP-DIM 

Installation Guide – DOC. 6638E 

Physical Description 

This section provides information on the connectors, 

controls, and indicators available on the CLS-EXP-DIM. 

CLS-EXP-DIM Overall Dimensions 

2 in

(51 mm)

6 3/8 in

(162 mm)

8 5/16 in

(211 mm)

7 5/16 in

(186 mm)

1/2 in

(13 mm)

1 5/8 in

(42 mm)

1 5/8 in

(42 mm)

3 1/16 in

(78 mm)

Ø 1/4 in

Ø (7 mm)

Ø 3/16 in

Ø (5 mm)

8 13/16 in

(224 mm)

5 in

(127 mm)

5 13/16 in

(147 mm)

3 3/16 in

(81 mm)

1 9/16 in

(40 mm)

 

 

CLS-EXP-DIM (Cover Removed) 

1

4

9

5

6

7

2

3

8

 

Connectors, Controls, and Indicators 

CONNECTORS, 

CONTROLS, AND 

INDICATORS 

DESCRIPTION 

FLUORESCENT 

OFF THRESHOLD 

(1) Recessed screwdriver-

adjustable trim pot behind 

removable cap, adjusts 

minimum brightness level 

STATUS 

(1) Red LED behind front 

panel, illuminates when load 

output is on 

POWER 

(1) Green LED behind front 

panel, indicates power is 

applied to the 

HOT

 terminal 

INPUT–CTRL 

(1) Captive screw terminal

1

control input from CLS(I)-C6 

Series, CLW-DIM Series

2

CLX(I)-DIM Series, GLX-DIM6, 

GLXX-2DIM8, DIN-1DIM4, or 

DIN-1DIMU4 dimmers; 

Presents a 25 watt load to the 

controlling dimmer;  

A maximum of five 

CLS-EXP-DIM modules may be 

connected to the controlling 

dimmer, which cannot be wired 

to control any other loads 

besides the CLS-EXP-DIM 

modules 

INPUT–NEUT 

(1) Captive screw terminal, 

neutral connection for control 

input 

(Continued on following page) 

Summary of Contents for CLS-EXP-DIM

Page 1: ...adjustment for setting minimum fluorescent dimming level Built in air gap relay at the output CLS EXP DIM Physical View 1 CLW Series devices must have a dedicated neutral 2 The CLS EXP DIM can only b...

Page 2: ...the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation This eq...

Page 3: ...le CLS EXP DIM Installation Guide DOC 6638E iLux Expansion Module CLS EXP DIM 3 Application The following diagram shows several CLS EXP DIM modules in a typical application CLS EXP DIM Modules in a Li...

Page 4: ...D INDICATORS DESCRIPTION 1 FLUORESCENT OFF THRESHOLD 1 Recessed screwdriver adjustable trim pot behind removable cap adjusts minimum brightness level 2 STATUS 1 Red LED behind front panel illuminates...

Page 5: ...ation Mounting Surface CLS EXP DIM Module Mounting Screw 8 Qty 4 Total Not Supplied Ensure proper ventilation Install device vertically on a vertical surface NOTE To prevent potential heat damage to d...

Page 6: ...ontrolling device The power indicator LED lights indicating that power is supplied to the module 4 Replace the cover and cover screws Set the Minimum Dimming Level Certain types of loads can flicker w...

Page 7: ...me incandescent loads can make noise when dimmed due to the size of the filament Try a different lamp manufacturer Lights flicker when at certain dimming levels Some types of loads cannot be dimmed be...

Page 8: ...any application other than that for which it was intended or if it has been subjected to misuse accidental damage modification or improper installation procedures Furthermore this warranty does not c...

Reviews: