ROC-2313 Reverse Osmosis Controller 

1 General 

The  instrument  is  a  combined  control  instrument  of  a  reverse  osmosis  controller  and  an  on-line 

conductivity  instrument.  It  can  perform  the  operation  test,  status  control  and  on-line  monitoring  of  water 

quality conductivity (combining PLC controller and conductivity meter). It takes multiple anti-interference 

measures, adopts unique process flow and graphical control panel with LED indicator lamp embedded, the 

interface is friendly; menu-driven operation is used, multiple groups of parameters can be set and modified, 

the requirements of automatic operation are met. 

 

2 Process Flow Selections

 

There are two typical operation  modes  for RO system (as shown  in Fig.1A and B).  This instrument 

can operate in both modes in A and B.   

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 

3 Functions and Main Technical Specifications 

Low feed protection:   

In  case  of  raw  water  supply  break-off,  the 

LOW  FEED  PRESS

  lamp  will  be  lightened,  the 

nixie  tube  will  display 

ALA

  and  the  buzzer  will  give  an  alarm,  the  controller  will  shut  down  the 

whole RO system. After that, the controller will keep detecting the low feed switch. When the water 

supply is resumed, the system will be restarted.   

Low pressure protection: 

  In case of low pressure, the 

LOW PRESS

 lamp will be lightened, the nixie tube will display 

ALA

 and the buzzer will give an alarm, the controller will shut down the whole RO system and try 

to  start  up  for  the  first  time  after  1  minute.  If  the  water  pressure  is  normal,  the  water  producing 

process  will  be  resumed.  If  the  start-up  fails  for  three  times,  the  system  will  come  into  a  dead-lock 

status. Press the ECS key(external control switch) or the reset key to exit and then restart.   

       

High pressure protection:   

In case  of  high pressure over limit, the 

HIGH PRESS

 lamp will be lightened, the  nixie tube 

will display 

ALA

    and the buzzer will give an alarm, the controller will shut down the whole RO 

 

Flush vale 

Flush valve 

Level of raw 

water 

 

Raw 

water 

tank 

Waste outlet 

Low 

press 

pump 

P

re

-p

ro

ce

ss

in

g

 1

P

re

-p

ro

ce

ss

in

g

 2

 

P

re

-p

ro

ce

ss

in

g

 3

 

Direct drain valve 

Safety   

filtering 

Low press protection

Inlet valve 

High 

press 

pump 

High press protection 

RO 

membrane

Pure 

water 

tank 

 

Fig. 1-A First level RO process flow with raw water tank

 

 

Fig. 1-B First level RO process flow with direct water supply

 

Safety 

filtering 

Low press protection

High press protection 

High 

press 

pump 

RO 

membrane

Flush valve 

Pure 

water 

tank 

Inlet valve 

Tap water 

Low 

press 

pump 

Waste outlet 

Low feed 

protection 

P

re

-p

ro

ce

ss

in

g

 1

 

P

re

-p

ro

ce

ss

in

g

 2

 

P

re

-p

ro

ce

ss

in

g

 3

 

Direct drain valve 

PDF 

文件使用

 "FinePrint pdfFactory Pro" 

试用版本创建

 

www.fineprint.com.cn

Summary of Contents for ROC-2313

Page 1: ...ase of low pressure the LOW PRESS lamp will be lightened the nixie tube will display ALA and the buzzer will give an alarm the controller will shut down the whole RO system and try to start up for the first time after 1 minute If the water pressure is normal the water producing process will be resumed If the start up fails for three times the system will come into a dead lock status Press the ECS ...

Page 2: ...mit the alarm will be set off Main technical specifications 1 Power voltage AC 220V 15 50Hz Power consumption 3W 2 Environment conditions 1 temperature 0 50 2 humidity 85 RH 3 Measuring range 0 200μS cm accuracy 1 5 level 4 Load capacity of output contact 3A 250V AC the magnetic valve should be driven through intermediate relay 5 Operation pressure of conductance cell 0 0 5Mpa 6 Medium temperature...

Page 3: ... inlet water operation pressure of high pressure pump is too low HIGH PRESS indication for over pressure operation of high pressure pump indicating that the outlet pressure of high pressure pump is too high INLET VALVE indication for inlet magnetic valve turning on indicating that the inlet magnetic valve is turned on M1 indication for low pressure pump operation indicating that the low pressure p...

Page 4: ...from up to down on the right 1 input terminal of high water level detection switch of pure water tank normally open close in case of low water level of pure water tank 2 input terminal of booster pump over pressure detection switch normally close switch off in case of over pressure 3 input terminal of insufficient low pressure detection switch normally open close at a preset pressure 4 input termi...

Page 5: ...please connect terminal 5 and 8 in short circuit 6 Reset signal may be connected to a reset button on the cabinet panel used for reset of high and low pressure alarms 8 a common terminal used jointly by the detection signals of terminal 1 2 3 4 5 and 6 Terminals from left to right in the middle 22 input wire of conductance electrode green wire 23 input wire of conductance electrode red wire 25 inp...

Page 6: ...ump Control execution Controller ROC 2323 Signal control Inlet magnetic valve Flush magnetic valve Detection common terminal Reset External control Low feed of raw water Low pressure High pressure High water level P ower inlet wire Master switch Over limit magnetic valve PDF 文件使用 FinePrint pdfFactory Pro 试用版本创建 www fineprint com cn ...

Page 7: ...is the default value the unit is second and the setting range is 0 249s If the setting is 90 then in each time that the pure water tank is full and the system stops or the system restart after low water level is detected the membrane will be flushed for 90s Flush interval C 03 03 is the default value the unit is hour and the setting range is 0 99h If the setting is 03 then the membrane will be flu...

Page 8: ... be connected to the same group of cable joint or terminal board with the power line 4 When the measurement cable needs to be lengthened it s recommended to use the cable provided by the original manufacturer When a longer distance is involved the length of the cable 30m should be agreed on before delivery and if the length is over 30m a transmitter should be used 10 Maintenance 1 The conductance ...

Page 9: ...w pressure pump Reverse osmosis high pressure pump Water Outflow m3 h Water Inflow m3 h 4040 Model 8040 Mod el Low pressure pump KW contactor A Low pressure membrane 1 05MPa KW contactor A High pressure membrane 1 55MPa KW contactor A 0 25 0 5 1 0 37 10 0 37 10 0 5 10 0 5 1 2 0 37 0 75 10 0 5 1 5 10 2 2 10 0 75 1 5 3 0 37 0 75 10 1 5 10 2 2 10 1 2 4 0 37 1 1 10 1 5 10 2 2 10 1 5 3 6 0 55 1 1 10 2 ...

Reviews: