74
FmaxTripT1(S)
Trip time of Level 1 Max. grid
frequency
{0, 0.16, 600.00}
GridF.Min1(Hz)
Protection threshold value of
Level 1 Min. grid frequency
{45.00, 59.30, 60.00}
FminTripT1(S)
Trip time of Level 1 Min. grid
frequency
{0, 0.16, 600.00}
GridF.Max2(Hz)
Protection threshold value of
Level 2 Max. grid frequency
{50.00, 61.00, 66.00}
FmaxTripT2(S
)
Trip time of Level 2 Max. grid
frequency
{0, 0.05, 600.00}
GridF.Min2(Hz)
Protection threshold value of
Level 2 Min. grid frequency
{45.00, 59.00, 60.00}
FminTripT2(S)
Trip time of Level 2 Min. grid
frequency
{0, 0.05, 600.00}
GridFmaxRecT(Hz)
Recovery threshold value of
Max. grid frequency
{49.00, 60.40, 66.00}
GridFminRecT(Hz)
Recovery threshold value of
Min. grid frequency
{45.00, 59.40, 60.00}
GridFRecT(S)
Recovery time of grid
frequency protection
{0, 300.00, 600.00}
GridV.Unbal(%)
Threshold value of grid
voltage unbalance
{0.1, 2.6, 10.0}