8
Technical data
Part numbers
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE Wiring
Regulations and any applicable Building Regulations.
ALC-PRM-VFC
DBB
Part number
Description
Detector
ALC-PRM-VFC
Ceiling Mounted Photocell
Accessories
DBB
Surface mounting box
UHS5
Programming IR handset
UNLCDHS
Universal LCD IR handset
Dimensions
See diagrams opposite
Weight
0.1kg
Supply Voltage
/- 10%
Frequency
50Hz
Maximum Load
10 Amp resistive and incandescent lighting
6 Amp fluorescent lighting and resistive
3 Amp compact fluorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting (switch primary
of transformer)
Fluorescent lighting (max 6 fittings
recommended)
For fluorescent lighting total power factor
correction capacitance must not exceed
40μF.
3 Amp fans and ventilation equipment
Switch SON lighting loads via a contactor
Minimum load 100mA
Power consumption
On 745mW, Off 264mW
Terminal Capacity
2.5mm
2
Temperature
-10ºC to 35ºC
Humidity
5 to 95% non-condensing
Material (casing)
Flame retardant ABS and PC/ABS
Type
Class 2
IP rating
IP40
Compliance
EMC-2004/108/EC
LVD-2006/95/EC