Basic programming 

Parameter 
Name 

Default 
Value 

0

 

1

 

2

 

3

 

UHS5 Handset Graphics 

Description 

 

 

Button Activation 

 

 

On 

 

On 

 

 

 

 

Turn lights on. 

Off  

 

Off 

 

 

 

 

Turn lights off. 

Lux on 
level 

(Switch 
level on) 

2, 5 & 7 

4, 6 & 9 

 

 

 

Lux level setting to prevent the luminaires being 
switched on if the ambient light level is sufficient 
(adjustable between 1 and 9). The luminaires will 
always be switched on at level 9.  

Lux off 
level 

(Switch 
level off) 

2, 5 & 7 

4, 6 & 9 

 

 

 

Lux level setting to switch the luminaires off the 
ambient light level goes above the setting 
(adjustable between 1 and 9). Level 9 will always 
keep the lights on. This setting can be used for 
“window row switching”. 

Note: the Lux Off Level value must always be 
greater than the Lux On Level value. 

Defaults 

 

 

 

 

 

Returns the unit to the default settings. 

Shift 

 

 

 

 

 

 

Use this button to select the settings in red and 
blue signified by the „Shift 1‟ and „Shift 2‟ LEDs 

Number of Shift key presses 

The functionality of the ALC-PRM-VFC is controlled by a number of parameters which can 
be changed or programmed by any of the following devices: 

UHS5

 Infrared Handset. See below for programmable functions. 

UNLCDHS 

Infrared Handset (with LCD). See user guide for full programming details. 

For most basic programming operations the UHS5 handset can be used and the following procedures 
are based on using this device. 
Point the handset at the Sensor and send the required programming commands to the unit as shown 
below. 
Valid commands will be indicated by a red LED flash. See page 1 for details of other LED responses. 

Note: other functions on the UHS5 which are not shown below are not applicable to this product.

 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

SHIFT 1  SHIFT 2 

Reviews: