5
Advanced programming
Parameter Name
Default Value Range / Options Description
UHS5 UNLCDHS
Detector Parameters
Lux time
0
0 (disabled)
1-99 minutes
To prevent nuisance switching, an adjustable time delay can be set. This requires
the light level to be maintained for the set time before changing from on to off, or
off to on.
Factory default
-
-
Restores factory default settings
User Modes
Override On
-
-
If the lights are off, sending the IR command will turn them on immediately and
revert to automatic operation using the manual timeout period .
Override Off
-
-
If the lights are on, sending the IR command will turn them off immediately. After
the manual timeout period (described above), the sensor will revert to automatic.
Cancel
-
-
Cancels the on or off override, returning the unit to normal operation.
Switching functions
Lux on level
(Switch level on)
9
1 to 9
For a higher
resolution a scale
of 101-199 is
available
Lux level setting to prevent the luminaires being switched on if the ambient light
level is sufficient.
Note: the Lux Level Off value must always be greater than the Lux Level On value.
Lux off level
(Switch level off)
9
1 to 9
For a higher
resolution a scale
of 101-199 is
available
Lux level setting to switch the luminaires off the ambient light level goes above the
setting.