9. Commissioning
YHC 700
The following popup will appear:
•
Controller model: specify whether YLC control units are accessed directly or via
the YHC 700.
•
Connection type: select the type of connection between MDM and YHC.
•
Slave address: YHC ModBus address (Default: 250)
•
Function: select whether YHC should be used for managing alarms only,
datalogger only, both or none of the two services.
9.2.4 YLCs configuration on the software for remote
management
Control systems can be:
● remotely managed with ClimaOffice
● remotely supervised by any software capable of:
○ sending ModBus commands to acquire data from the YLC in field
○ managing data sent by YHC via HTTP/HTTPs
In this document we will refer to ClimaOffice as the Coster Group solution for the remote
management of control systems made with YHC.
9.2.4.1 Connecting to YLC via GSM
To configure the YLCs from ClimaOffice, load the relevant application mimic panels in
ClimaOffice and create the corresponding installation, making sure you specify the following
configuration parameters:
●
Controller connection
→ GSM connection
●
SIM No.
→ Phone number of the MDM 232 modem
●
Controller access code
: Modbus slave address of the controller
WARNING
: In control systems that include both and MDM and a YHC, it is not possible to
access YLC controllers via STE 000.
32