Network-Manager Modbus 

YHC 700 

 

Data Sheet 

D33481-A  10/02/2020 

 

Summary of Contents for YHC 700

Page 1: ...Network Manager Modbus YHC 700 Data Sheet D33481 A 10 02 2020 ...

Page 2: ...2 Communication with field devices 13 5 3 Bridging between YLC controllers 14 5 4 Data logging instantaneous data logger 14 5 5 YLC data caching 14 5 6 Sending alarms 14 5 6 1 Sending alarms via e mail 14 5 6 2 Sending alarms via HTTP HTTPs 14 5 6 3 Sending alarms using the MDM 232 modem 15 5 7 Monitoring data reading 15 5 8 Datalogging dei dati di monitoraggio 15 5 9 M BUS devices integration 15 ...

Page 3: ...1 1 Field devices commissioning 30 9 1 2 YHC Configuration 30 9 1 3 YLCs configuration on the software for remote management 30 9 2 Commissioning a control system YHC MDM 31 9 2 1 Field devices commissioning 31 9 2 2 YHC Configuration 31 9 2 3 MDM 232 Configuration to work with YHC 31 9 2 4 YLCs configuration on the software for remote management 32 9 3 Commissioning a monitoring system 33 9 2 1 F...

Page 4: ...l requirements If the device is not installed commissioned and maintained correctly according to the instructions contained in this manual then it may not work properly Failure to install put into service and maintain the device in accordance to the instructions in this manual can cause equipment faults and can cause hazards to the user and other exposed persons IMPORTANT BEFORE YOU START ANY WORK...

Page 5: ...232 In the second and third cases the system remote management and configuration is supported via ethernet only 2 Technical specifications The following tables show all the specifications relating to the device 2 1 Hardware N DESCRIPTION 1 RS 232 BUS used for connection with the MDM 232 modem ONLY 2 RS 485 EXPANSION BUS 1 for remote control devices 1 for monitoring devices 1 Ethernet port for comm...

Page 6: ...IPTION 0 30 Multimeters of the following types IME Nemo D4 Le 1 phase or 3 phase IME Conto D4 Pr MID Electrex Atto D4 1 phase or 3 phase MFD 448 0 10 GSP 485 0 40 Heat meters among the following M BUS meters Costergroup IEF 176 Costergroup IEF 276 e Sensus PolluStat and or Modbus meters Isoil IFX F100 0 3 CSW 868 0 3 BRG 868 C 0 5 CDP 1x0 M Bus Modbus converter for integrating up to 8 devices 1 2 ...

Page 7: ...et the requirements of their installations and that cabling conforms to current national and local regulations If a cable is damaged it must be replaced by the producer the technical service or any other person the like WARNING the RS 232 bus used to connect YHC to MDM 232 must be shorter than 3 meters WARNING when connecting YHC to MDM please make sure that the YHC TX terminal is connected to the...

Page 8: ...3 Electrical installation YHC 700 3 2 Connection examples Example 1 control system with multiple YLCs on the 485 bus and supervision via 3G modem 8 ...

Page 9: ...ical installation Example 2 control system with multiple YLCs on the Ethernet bus supervision via Ethernet Example 3 control system with multiple YLCs on the Ethernet bus and on the RS 485 bus supervised via Ethernet 9 ...

Page 10: ...3 Electrical installation YHC 700 Example 4 monitoring system 10 ...

Page 11: ...llation Example 5 hybrid system NOTE RUT 001 has been used in the above examples only for explanation purposes any generic router can be used WARNING YLC 880 MUST be configured with RS 485 connectivity see YLC 880 data sheet 11 ...

Page 12: ...s LED 1 power supply status always ON LED 2 communication on RS 232 port blinks when transmitting receiving LED 3 communication on RS 485 port no 1 blinks when transmitting receiving LED 4 communication on RS 485 port no 2 blinks when transmitting receiving 12 ...

Page 13: ...et during its configuration the maximum communication speed allowed by YHC is 500kbps but it can be lower to consider the maximum speed supported by the connected devices as well NOTE from the FW version 2 0 YHC can communicate with YLC at two different baud rates 9600 or 19200 depending on the control unit settings 2 YHC can also manage YLC with different baud rates on the same control bus The RS...

Page 14: ...requests the control unit data YHC can send it immediately From FW 2 0 YLC data caching can be disabled 5 6 Sending alarms In control systems and hybrid systems 4 you can decide to manage YLC alarms through the YHC700 YHC700 can send alarms only via its ethernet port in two possible ways via e mail via HTTP HTTPs post command When configuring YHC700 you can specify which of the two modes you want ...

Page 15: ...ending by SMS you can specify Up to 3 numbers of SMS recipients 5 7 Monitoring data reading In the case of energy monitoring systems YHC700 periodically queries the devices in the field the acquisition periodicity can be selected during the configuration phase for each of the supported device types The acquired data can then be consulted through a supervisor interface if the option to send data to...

Page 16: ...ces in the field similarly to what was done by GTW 485 in case YHC700 is connected to YLC controllers the data sent are those of the instantaneous data logger It is possible to send data to different cloud servers for example you could send YLC data to one server and those of the wireless sensors to another specifying for each also the periodicity of the sending which is totally independent from t...

Page 17: ... be remotely managed with ClimaOffice WEBGarage remotely supervised or any software able to send ModBus commands to read the YLC in field manage the data received from the YHC via HTTP HTTPs Monitoring systems can only be supervised through YHC web pages see chapter 10 WEBGarage or any software able to send ModBus commands to read the YLCs in field manage the data received from the YHC via HTTP HT...

Page 18: ... WPA2 PSK USB 2 0 interface compatible with USB 1 1 upward compatible with USB 3 0 frequency range 2 4 GHz 13 channels mime technology MIMO Contact the Cost Group technical assistance for further information 7 1 2 Connection via USB cable 1 Connect the PC to YHC with a USB cable USB to micro USB 2 From a web browser open the YHC URL indirizzo ip dell yhc 8080 default http 192 168 7 2 8080 3 Access...

Page 19: ...u can configure YHC using the HTML pages as shown below NOTE to access the Configuration pages you must be logged in with the following credentials username service password CosterGrp267837 The password can be changed in a dedicated menu of the YHC WEB Pages see chapter 7 2 3 6 7 2 1 Building Control This menu provides access to the WEB pages for configuring the YLCs and how to manage their alarms...

Page 20: ...it is enabled or not this can be useful in the support phase to isolate any source of errors The connection mode RS485 bus or Ethernet 5 Default RS 485 The Modbus address Default 1 The IP address if any if the specified connection mode is Ethernet o Whether the instantaneous data logger cloud sending is enabled on that controller Default No A short description used in the diagnostic web pages NOTE...

Page 21: ...hentication or an SMTP server with STARTTLS authentication Default ClimatelCloud o A short description of the sender o The sender email address and in case of SMTP server the password required for authenticating o Up to 5 receivers email addresses In case of http sending o The URL address of the server the alarms will be sent to o The Key required to identify the installation the alarms refer to 7...

Page 22: ...ration NOTE L indirizzo bridge è presentato nella forma BRGC xx id yy dove xx è l indirizzo slave del concentratore e yy è l id del bridge collegato Il tempo di polling può essere diverso dal tempo con cui YHC700 comunica i dati al supervisore il polling può anche essere continuo In this section you can specify The number of energy meters managed from 0 to 30 Default 0 The polling time how often Y...

Page 23: ... Whether it is enabled or not The pulse counter model to date only GSP 485 see section 2 4 2 The pulse counter address The address of the BRG868 through which the pulse counter is read or the option of the pulse counter direct connection the RS485 bus Default bus 485 The pulse counting mode Default Cumulated pulses Possible multipliers to be applied to pulse inputs 1 and 2 Default 1 A short descri...

Page 24: ... the option of the energy meter direct connection the RS485 bus Default bus 485 o For M BUS heat meters the address of the gateway through which the meter is read Default 0 o A short description 7 2 2 2 M BUS gateways configuration In this page you can Read the M BUS gateways main info Remove the last M BUS gateway of the list Add a new gateway by specifying o The gateway model see chapter 2 4 2 o...

Page 25: ... sent that refers to that specified installation The transmission interval Default Disabled 7 2 2 4 Datalogger configuration In this page for each monitoring device type you can select wether to log its data or not Default disabled 7 2 2 5 Datalogger data export In this page you can Specify how to export the monitoring datalogger USB pen or FTP server on YHC Default FTP Server The timeframe starti...

Page 26: ...meters 7 2 3 1 Network In this page you can configure the YHC 700 network parameters such as The YHC 700 IP address dell YHC700 specifying also whether it is a static IP or not Default static The primary and secondary DNS used if any Any gateway These data are saved in the installation network configuration file NOTE 26 ...

Page 27: ...t YHC700 should be considered a bus terminator 7 2 3 3 Language and Timezone This page allows you to set the language used in the HMTL pages as well as the time zone to be considered when recording the data that will be sent to the cloud and or that will be used in the dataloggers YLC instantaneous datalogger or the monitoring device datalogger NOTE after changing the language you may need to relo...

Page 28: ... this option is available by enabling the NTP relay flag ClimatelCloud the MDM 232 if existing 7 2 3 5 Site information In this page you can specify a description for the installation site This description will be particularly useful to identify the site on the supervisor 7 2 3 6 Software In this page you can update YHC software either remotely via FTP server or locally from the USB pen 7 2 3 7 Ch...

Page 29: ...e button to start the update process Should the update procedure fail the user is notified and the previous software remains active on the device NOTE when a software update is requested YHC 700 connects via http to an external website to download the latest software available This mechanism requires YHC700 to be connected to the Internet 8 2 Aggiornamento software da locale From release 2 0 YHC s...

Page 30: ...rvised by any software capable of sending ModBus commands to acquire data from the YLC in field managing data sent by YHC via HTTP HTTPs In this document we will refer to ClimaOffice as the Coster Group solution for the remote management of control systems made with YHC To configure the YLCs from ClimaOffice load the relevant application mimic panels in ClimaOffice and create the corresponding ins...

Page 31: ...to connect the RS485 port 1 to the RS485 bus of the YLCs connect the RS232 port to the RS232 bus of the MDM 232 modem WARNING when connecting the MDM 232 to YHC make sure the TX termination of the MDM is connected to YHC TX termination and that the MDM RX termination is connected to YHC RX termination 9 2 2 YHC Configuration Configure YHC as described in chapter 7 9 2 3 MDM 232 Configuration to wo...

Page 32: ...e of sending ModBus commands to acquire data from the YLC in field managing data sent by YHC via HTTP HTTPs In this document we will refer to ClimaOffice as the Coster Group solution for the remote management of control systems made with YHC 9 2 4 1 Connecting to YLC via GSM To configure the YLCs from ClimaOffice load the relevant application mimic panels in ClimaOffice and create the correspondin...

Page 33: ...he slave address with the string TCP Example 1 TCP 9 3 Commissioning a monitoring system Commissioning in this case involves the following steps 1 Commissioning of the field devices 2 YHC configuration 9 2 1 Field devices commissioning The devices are installed according to the instructions provided in each device data sheet they are connected to the YHC by means of the RS485 2 bus NOTE BRG C and ...

Page 34: ...dges concentrators RS 485 bus communication statistics 10 2 Diagnostics This page provides detailed information and the possibility to take spot readings on some devices The diagnostics page is divided into three sections diagnostics of radio devices o Operating information and data read by concentrators sensors and radio bridges are displayed diagnostics of monitoring devices o Information concer...

Page 35: ...in particular the national and local regulations concerning low voltage electrical systems 12 Directives EMC directive 2014 30 EU General product safety 2001 95 EU Restriction of the use of certain hazardous substances in electrical and electronic equipment 2011 65 EU 13 Regulations of conformity EN 61326 1 2013 Electromagnetic Compatibility EN 61010 1 2010 A1 2019 Electrical Safety Rev Date Autho...