37
FRYO PI
COSMOGAS
7 - USO
Parameter
Description
Unit of
measure
Range
Factory
value
00
System control mode (N/A)
/
Leave at 0
0
01
External ON / OFF switch: must be connected between ES
and GND terminals (Figure 5-10). This switch also turns off
the DHW.
/
00 (input disabled),
01(input enabled)
0
02
Water flow switch activation delay after switching on the pump
sec
0 (water flow switch control is disabled),
1 ... 60 (flow switch activation delay)
60
03
Heating storage (do not change) (N/A)
/
0 (no), 1(yes)
0
04
Cooling storage (do not change) (N/A)
/
0 (no), 1(yes)
0
05
DHW or heating priority switch
(do not change) (N/A)
/
0 (DHW), 1 (heating)
0
06
Refrigerant collection (do not change) (N/A)
/
0 (off), 1 (compressor system 2 ON),
2 (compressor system 1 or single ON)
0
07
Block function (do not change) (N/A)
week
00...99
00
08
Operating mode
/
0 - Only DHW (to control the ON/OFF switch
of the DHW function, use the ES and
GND contact in Figure 5-10);
1 - Cooling and Heating (to control the ON/
OFF switch of this two functions, use the
relative contact CS-GND and HS-GND of
Figure 5-10);
2 - All function are active. The “Tw” sensor
must be connected (to control the ON/
OFF switch of this functions, use the
relative contact of Figure 5-10);
3 - Only heating (Caution!!! In this mode
the contact HS-GND of Figure 5-10 is
disabled, so the function is continuously
active);
4 - Heating and DHW. The “Tw” sensor must
be connected (Caution!!! In this mode the
contacts HS-GND and ES-GND of Figure
5-10 are disabled, so the functions are
continuously active);
1
09
Compressor modulation band with respect to the setpoint
temperature. The band is positive in heating and negative in
cooling.
°C
2...10
2
0A
Maximum duration for minimum compressor speed. When
the supply is higher than the setpoint value, the compressor
speed will be reduced. The compressor will be switched off
after having worked continuously at the minimum value for the
time set in this parameter. After the set time has elapsed, the
compressor restarts after 3 minutes.
Min
10...60
30
Press the key to access the following parameters:
Parameter
Description
Unit of
measure
Range
Factory
value
A1
Type of pump control
/
0 (pump works when the compressor works),
1-15 (when the compressor is stopped, the
pump switches on and off for the period set
here between 1 and 15 minutes),
16 (as long as there is a demand, the pump
is always on)
16
The “Advanced Mode” parameters are listed in the following tables:
Summary of Contents for FRYO 6PI
Page 2: ......
Page 58: ...58 FRYO PI COSMOGAS...
Page 59: ...59 FRYO PI COSMOGAS...
Page 60: ...COSMOGAS s r l Via L da Vinci 16 47014 MELDOLA FC ITALY info cosmogas com www cosmogas com...