AD-14
n
n
When unit operates by pulse load, attach the external capacitor at
output line which corresponds to peak value of pulse current (If
the pulse current is drawn directly, it will shorten the life time of ca-
pacitor installed in the power supply).
Due to the nature of a pulse load, a power supply may make a
sound (noise). If the unit is used in an quiet place, consult factory
for the load condition in advance.
Note 1. Select an external capacitor with capacity above the line
in the graph.
Note 2. Make sure ripple current of an external capacitor is allowable.
Note 3. Select the electrolytic capacitor with a capacity over 35V
of its rated voltage.
Note 4. When the load current draws continuously, external ca-
pacitor is not necessary.
l
l
AD240
AD480
l
AD960
5 Peak Loading
AD
Unit type
Instruction Manual
AC-DC Power Supplies Enclosed type
June 29, 2011