AD-11

l

l

l

AD480

AD960

AD480

Remarks:

n

n

n
n

n

n

When short/overcurrent condition continues more than 10 sec-

onds, average overcurrent circuit (operated at 110% of rated cur-

rent) operates, and it reduces the current by hang of voltage.

When cause of activation of overcurrent protection is removed,

the output will be automatically recovered.

The overvoltage protection circuit is built-in and comes into effect

at 115 - 140% of the rated voltage. The AC input should be shut

down if overvoltage protection is in operation. The minimum inter-

val of AC recycling for recovery is 5 minutes.

Please avoid applying the over-rated voltage to the output termi-

nal. Power supply may operate incorrectly or fail.In case of oper-

ating a motor etc. , please install an external diode on the output

terminal to protect the unit.

Adjustment of output voltage is possible by using potentiometer.

Output voltage is increased by turning potentiometer clockwise

and is decreased by turning potentiometer counterclockwise.

The ground terminal of remote ON/OFF circuit is connected

with -V output terminal.

For a receiving inspection, such as Hi-Pot test, gradually increase

(decrease) the voltage for the start (shut down). Avoid using Hi-

Pot tester with the timer because it may generate voltage a few

times higher than the applied voltage, at ON/OFF of a timer.

2.4 Overvoltage protection

2.5 Output voltage adjustment range

2.6 Remote ON/OFF

2.7 Isolation

The recovery time varies depending on input voltage.

Between RC and RCG: Output voltage is ON at High” level or

open circuit.

Between RC and RCG: Output voltage is OFF at Low” level or

short circuit.

When RC terminal is Low” level, fan out current is 5mA.

l

l

AD480

AD960

n

If the unit is tested on the isolation between input & output and

output & FG, remote ON/OFF must be shorted to output.

(1) Over 45

(Ambient temperature)

(2) Poor ventilation

(3) Excessive output current for over 10 seconds

2.8 Thermal protection

n

Thermal protection is built-in. If this function comes into effect,

shut down the output, eliminate all possible causes of overheat-

ing, and drop the temperature to normal level. Output voltage re-

covers after applying input voltage. To prevent the unit from over-

heating, avoid using the unit in a dusty, poorly ventilated environ-

ment.

3 Series Operation and

Parallel Operation

3.1 Series operation

3.2 Parallel operation/master-slave operation

n

n
n

Series operation is available by connecting the outputs of two or

more power supplies, as shown below. Output current in series con-

nection should be lower than the lowest rated current in each unit.

Parallel operation is not possible.

(a)

(b)

Redundancy operation is available by wiring as shown below.

l

AD240 AD480

AD

I

2

I

1

I

3

-

-

+

Power
supply

Power
supply

+

Load

Instruction Manual

AC-DC Power Supplies Enclosed type

June 29, 2011

Summary of Contents for AD240

Page 1: ...Forward converter Forward converter Forward converter 10 0 10 0 5 0 170 200 54 Circuit method operation availability 1 1 Yes Triac Triac Triac FR 4 FR 4 FR 4 Yes Yes Yes Yes Yes Yes Rated Basic Characteristics Data Model frequency Switching A current Input Series Parallel Parallel operation PCB Pattern Inrush protection current Material Double sided sided Single Series operation kHz AD 8 AD June 2...

Page 2: ... 2 8 Input voltage range Series operation Installation method Inrush current limiting Parallel operation master slave operation Derating Mounting screw Overcurrent protection Overvoltage protection Output voltage adjustment range Remote ON OFF Isolation Thermal protection AD 10 AD 10 AD 10 AD 11 AD 11 AD 11 AD 11 AD 11 AD 12 AD 12 AD 12 AD 13 AD 11 AD 11 AD 10 AD AC DC Power Supplies Enclosed type...

Page 3: ...ection from inrush current By changing the input voltage selector between VS1 VS2 short or open either AC100V or AC200V is possible The unit is shipped from the factory for AC200V open condition In the case of AC100V install the short piece between VS1 and VS2 If the wrong connection is made for short open the power supply may be damaged The input voltage should be within the above range The range...

Page 4: ...ied voltage at ON OFF of a timer 2 4 Overvoltage protection 2 5 Output voltage adjustment range 2 6 Remote ON OFF 2 7 Isolation The recovery time varies depending on input voltage Between RC and RCG Output voltage is ON at High level or open circuit Between RC and RCG Output voltage is OFF at Low level or short circuit When RC terminal is Low level fan out current is 5mA l l AD480 AD960 nIf the un...

Page 5: ... at the same time Adequate wiring design for in put circuitry is required such as circuit pattern wiring and current capacity for equipment In parallel operation the maximum operative number of units is 5 When remote sensing is used in parallel operation the sensing wire must be connected ONLY to the master lAD960 nIn parallel operation please connect diode to the side of the out put circuit If di...

Page 6: ...f the unit needs to be mounted in a non listed position 2 Derating curve 100 load factor means 960W of output power n n n n n Cooling by Forced air Do not block the ventilation hole so that the air ventilates equally Cooling by convection Operative ambient temperature varies depending on the cooling method Please refer to the following derating curve Keep isolation distance between screw and inter...

Page 7: ...sed in an quiet place consult factory for the load condition in advance Note 1 Select an external capacitor with capacity above the line in the graph Note 2 Make sure ripple current of an external capacitor is allowable Note 3 Select the electrolytic capacitor with a capacity over 35V of its rated voltage Note 4 When the load current draws continuously external ca pacitor is not necessary l l AD24...

Reviews: