HomeVision® Pro
© Corroventa Avfuktning AB
2021.02
35 (44)
Reconfigure unit (by regulation parameters), VentoVind™
In the status view, normal view, first press
<Setup>
and then <
▼
> twice to get to the Settings
view.
In the settings view, press
<Select>
and then <
▼
>
so that the ”Reconfigure unit” row is
marked.
Press
<OK>
to select this function.
The panel now asks the user to select the unit to
be reconfigured. If required, press <
▼
> to scroll to
the relevant unit. If the relevant unit is already
marked, press
<OK>
to continue.
The Start level / Stop level
- the settings for which
ratio the system is to start and stop the fan at.
Once it has started, it works normally until the
humidity indoors and outdoors is equal, which is
reason that the Stop value is less than the Start
value.
Fan type
regulates what is connected and can be
set for AC, EC fan and CR (control relay) which
means that the fan is controlled via relay.
Reconnection in the Control unit is also required
when replacing the fan.
Start/Top speed
controls at which speed the fan is
to start respectively how fast it may run.
Top speed level
controls at which ratio the fan is
to reach its defined top speed.
Fan delay
controls the motor damper delay that
the fan is to start at. If the motor damper has not
had time to open before the fan starts, there is a
risk of damper noise.
Alarm MGP/days
controls the level and the
duration required for an alarm to be presented on
the display. This is usually set to 1.0/5, which
means that if the MGP level exceeds 1 for five days
in a row, the alarm is triggered to notify the user
of the situation.
Min Temp
is the minimum permitted Outdoor
temperature at which the system may work.