background image

STANDARD RECOMMENDED PROCEDURE 003-873 | ISSUE 2 | APRIl 2016 | PAGE 18 OF 18

Corning Optical Communications LLC • PO Box 489 • Hickory, NC 28603-0489 USA 

800-743-2675 • FAX: 828-325-5060 • International: +1-828-901-5000 • www .corning .com/opcomm

Corning Optical Communications reserves the right to improve, enhance, and modify the features and specifications of Corning Optical Communications products 

without prior notification. A complete listing of the trademarks of Corning Optical Communications is available at www.corning.com/opcomm/trademarks. All other 

trademarks are the properties of their respective owners. Corning Optical Communications is ISO 9001 certified. © 2011, 2016 Corning Optical Communications. 

All rights reserved.

12 .  Connector Care and Cleaning

• 

Always keep dust caps on connectors and adapters when not in use.

•  Ensure dust caps are clean before reuse.
• 

Use optical cleaning materials as standardized by your company.

• 

Clean the connector before every mating, especially for test equipment patch cords 

(jumpers).

• 

A minimum level of cleaning is listed below. Local procedures may require  more rigorous 

cleaning methods.

WARNING: 

Isopropyl alcohol is flammable with a flashpoint at 54ºF. It can cause irritation to 

eyes on contact. In case of contact, flush eyes with water for at least 15 minutes. Inhalation 

of vapors irritates the respiratory tract. Exposure to high concentrations has a narcotic effect, 

producing symptoms of dizziness, drowsiness, headache, staggering, unconsciousness and 

possibly death.

Step 1: 

Remove plugs from the connector adapter.

Step 2: 

Wipe the connector ferrule twice with a lint-free wiping material moistened with 

isopropyl alcohol. Then wipe across the end of the ferrule.

Step 3: 

Repeat previous step with a dry wipe.

If necessary to clean the connectors mated to the rear of the connector adapters, rotate the 

latch on the distribution field and swing the panel to the open position as shown in Figure 8. 

Clean and remate the connectors. Close and latch the panel when complete.

13 .  Securing the Cabinet

When all work operations inside the cabinet are complete, secure 

the door.

Step 1: 

Replace the door, if previously removed, See “Opening 

the Cabinet” on page 7.

Step 2: 

Close the door and, using a 216B tool, rotate the 

tool to the right to lock the door latch (Figure 27). For 

additional security, insert a padlock through the holes 

in the hasp around the 216B lock.

KPA-0888

Figure 27

 — Lock the Door

Summary of Contents for OptiTect

Page 1: ...o 432 Fibers on a Wall 6 5 2 Mounting Cabinets with up to 432 Fibers into a Rack 6 5 3 Mounting Cabinets with more than 432 Fibers to the Floor 6 6 Opening the Cabinet 7 7 Grounding the Cabinet 7 8 Ma...

Page 2: ...nstalled P N FDH GRND KIT Feeder and distribution cable installation kit Feeder and distribution cable strain relief kit Wall mount and rack mount kit Only included with smaller indoor cabinet Install...

Page 3: ...pment and supplies 2 2 Materials Mounting hardware to attach the cabinet to the wall is not provided The hardware needed is dependent upon the surface to which the cabinet is being installed 3 Storage...

Page 4: ...can alter the transmission characteristics of the cable the cable may have to be replaced Step 5 If the unit shipped with cables preinstalled clip the ties from the cables Roll out the cables when re...

Page 5: ...View Top View 144 to 432 fiber cabinets 576 to 864 fiber cabinets Cabinet installed into frame Parameter 144 288 fiber unit 432 fiber unit 576 864 fiber unit Height H inches 31 33 26 25 w o splice ho...

Page 6: ...inet and hook the mounting bracket over the bracket on the wall Figure 6 IMPORTANT Lower edge of the cabinet or splice chamber should be approximately 36 inches above the floor Step 5 Screw the bottom...

Page 7: ...et Step 1 Unlock panel and swing it open Step 2 Open the splice chamber door and pedestal skirt if equipped with these items Slide splice trays out Step 3 Bring ground cable up through the grommet in...

Page 8: ...put fiber field and the output fibers will be mated to the front of the storage parking panel Step 1 Once service has been ordered remove the appropriate connector from the stored parked position clea...

Page 9: ...re sharply than the minimum recommended bend radius Do not apply more pulling force to the cable than specified Do not crush the cable or allow it to kink Doing so may cause damage that can alter the...

Page 10: ...o allow for cable adjustment during braided tubing installation and strain relief activities Cabinet Capacity Distribution Cable s F2 Feeder Cable s F1 144 fibers 9 5 feet 10 5 feet 288 fibers 10 feet...

Page 11: ...tment D Top of Cabinet 1 5 to 3 5 feet 4 feet All Cabinet Versions to 1 Full Loop of Fiber Around Splice Tray Sub units in Braided Tubing Refer to Table for Cable Sheath Removal Length 4 feet All Cabi...

Page 12: ...e end of the fiber s with the electrical tape Figure 12 Figure 12 Attach Plastic Rod Step 3 Push the braided tubing over the rod Figure 13 Figure 13 Install Braided Tubing Step 4 Slide tubing toward t...

Page 13: ...17 Remove Extra Slack Step 8 Secure the other end of the braided tubing Figure 18 Cut off the plastic rod Wrap electrical tape around the end of the braided tubing IMPORTANT Approximately 48 inches of...

Page 14: ...he teeth on the upper plate into the sheath Step 4 Wrap the grounding connector and split portion of the sheath with a few wraps of vinyl tape Step 5 Attach the ring terminal of the ground wire over t...

Page 15: ...ing the ground hardware Step 2 If there is a central member present install the central member restraint clip as shown in Figure 22 Trim the central member flush with the bottom of the restraint clip...

Page 16: ...in the splice housing with Distribution splicing in subsequent trays above Two sub units jacketed or braided tubing with three 12 fiber ribbons per sub unit can be strain relieved to each feeder splic...

Page 17: ...the organizer and routing slack around the organizer and within the interior of the tray Figure 26 Step 6 Reinstall the splice tray cover ensuring the tray cover is captured beneath the retaining tabs...

Page 18: ...ng methods WARNING Isopropyl alcohol is flammable with a flashpoint at 54 F It can cause irritation to eyes on contact In case of contact flush eyes with water for at least 15 minutes Inhalation of va...

Reviews: