Configuration Command Class
No. Configuration
parameter
Default Range
Encoding
1
Temperature
Report threshold
0.5°C
0.1 to 10°C
2 bytes
1 = 0.1°C
100 = 10.0°C
2
Set-point display
resolution
0.5°C
From 0.1 to
10°C in 0.1°C
steps
2 bytes
1 = 0.1°C
100 = 10.0°C
3
Min set-point and
override limit
12°C
From min
0°C to max
setpoint/
override limit
2 bytes
0 = 0°C
40 = 40°C
4
Max set-point and
override limit
28°C
From min
setpoint/
override limit
to max 40°C
6
Setpoint control
function
Enabled Disabled /
enabled
1 byte
0 = Disabled
1 = Enabled
7
Temporarily over-
ride scheduler
Enabled Disabled /
enabled
8
Setpoint Type in
Thermostat_
Setpoint_Reports
Heating Heating #1,
Cooling #1,
Auto
Changeover
1 byte
1 = Heating #1
2 = Cooling #1
10 = Auto
Changeover
9
LED on time
100ms 100 to
500ms in
100ms steps
1 byte
1 = 100ms
5 = 500ms
5
LED Flash period
1s
0 to 65535
seconds
2 bytes
10 Number of LED
flashes (duration)
5
0 to 255
flashes
1 byte
11
LED Color
Green
Green, Red
1 byte
0x01 = Green
0x02 = Red
GB
qheat
DTHERMZ5 10/2015
11
Installation & User Guide qheat room sensor