Rooftop Packaged Service Manual MAINTENANCE
91
2. Take out the cover
plate.
Unscrew the screws fixing cover
plate (indicated by arrows) to take it
out.
3. Take out the fan
blade.
Unscrew the screw (indcated by the
arrow) fixing fan to take the fan out.
Note:
Fix fan blade when unscrew the
holding bolt to avoid fan blade from
rotating and thereby injury to people is
caused.
4. Take down the
motor from the
bracket.
Remove the holding bolt of motor
firstly and then remove motor from
bracket.
Note:
Loosen power cord fixed by
bundles before removing motor.
5. Fix the new motor
on to the bracket.
Put the repaired or replaced motor
onto brakcet as the direction during
removing. Then screw down the
holding bolt with a wrench.
Note:
Please keep the motor level and
vertical during installation. After that,fix
the power cord with bundles at original
locations.
6. Install and fix fan
blade.
Re-install fan blade and screw down
the holidng bolt indicated by the
arrow with a wrench
Note:
Moment of force should be within
8-12N during screwing down bolt. After
that, please charge glue into gap
between bolt and hole to avoid loose of
it.
Summary of Contents for CH-IRT05NM
Page 4: ...Rooftop Packaged Service Manual PRODUCT 1 PRODUCT ...
Page 10: ...Rooftop Packaged Service Manual CONTROL 7 CONTROL ...
Page 12: ...Rooftop Packaged Service Manual CONTROL 9 1 2 HEATING OPERATION ...
Page 36: ...Rooftop Packaged Service Manual INSTALLATION 33 INSTALLATION ...
Page 39: ...Rooftop Packaged Service Manual INSTALLATION 36 CH IRT08NM CH IRT15NM ...
Page 49: ...Rooftop Packaged Service Manual INSTALLATION 46 CH IRT15NM CH IRT15NM ...
Page 50: ...Rooftop Packaged Service Manual MAINTENANCE 47 MAINTENANCE ...
Page 110: ...Cooper Hunter International Corporation www cooperandhunter com ...