Ambient Atmosphere Requirements
Temperature
32
0
F to 104
0
F (0
0
C to +40
0
C)
Humidity
0 to 95% non-condensing
Mounting
Location and Spacing
The Universal Source Controller models are all fully convection
cooled, therefore it is vitally important to ensure that each
unit is installed in a ventilated location that permits sufficient
airflow and provides the correct ambient conditions.
Ensure that the minimum distances to walls and other
equipment shown in the diagrams below are maintained.
Also ensure that the stated ambient atmosphere requirements
are not exceeded.
Refer to ‘Important points for consideration’ when choosing a
mounting location.
Upper Raceway
Lower Raceway
Airflow
Airflow
Airflow
Main
Supply
Isolator
8 in.
(200 mm)
Minimum
8 in.
(200 mm)
Minimum
5 in.
(130 mm)
Minimum
14 in.
(360 mm)
Minimum
Distance to
Ceiling
14 in.
(360 mm)
Minimum for
Door Access and
Cooling
5 in.
(130 mm)
Minimum