Total Load Per Channel

The load on each channel 

must not exceed 16A

.

Load Wire Gauges 

Load wiring must be sized according to the nature of the 

channel load(s) and with strict regard to regulations and codes 

in force within your locality. The maximum permissible wire 

gauges accepted by the connector blocks are:

Solid wire:  

10 AWG (6 mm

2

Stranded wire:   12 AWG (4 mm

2

)

Earth Connections

Earth connections for each channel are available at the 

connector blocks located at the top of each wireway:

To Insert a Wire 

1. 

Strip roughly a quarter inch (6 mm) of insulation from the 

wire end. 

2.  Place a small flat blade screwdriver all the way into the 

upper rectangular hole (keep the tip of the screwdriver 

against the top edge of the hole).

3. 

Press the screwdriver tip downwards towards the base of 

the connection block and push the stripped wire into the 

large circular hole.

4.  When the wire is in place, release the screwdriver and 

check that the wire is firmly held by the internal spring clip.

High Voltage Load Wiring Flows

A knockout (diameter 2.42 inchs /61.5 mm) is provided above 

each load wireway within the top panel of the chassis. Use 

suitable conduits and couplers. Please see the wiring flow 

diagram on page 8.

Typical Load Connections

The examples below show some of the most typical loads and 

the way in which they are connected to a Source Controller 

circuit.

Defining Load Types

The type of load placed upon each channel must be defined 

within the Configuration menu of the control panel. For further 

details on how to do this, please refer to the accompanying 

System manual. 

Standard Dimmable Load

Non-Dim Load

Constant Load

2 Wire Fluorescent Dimmable Ballast (E.g. Advance 

 

Mark X™)

3 Wire Fluorescent Dimmable Ballast (E.g. Lutron

®

 Hi-

Lume

®

 Or Eco-10™)

4 Wire Fluorescent Dimmable Ballast (E.g. 0-10 VDC 

Control)

Load Earth Connector Blocks

[Neutral - White]

[Neutral - White]

[Neutral - White]

[Neutral - White]

[Neutral - White]

[Neutral - White]

Ballast

Lutron® 

Ballast

0-10V  

Ballast

Lamp

Lamp

Lamp

[Dimmed Hot - Black]

[Dimmed Hot - Black]

[Dimmed Hot - Black]

[Dimmed Hot - Black]

[Channeled Hot - Black]

0-10V Control Output - Violet

0-10V Common - Grey

[Dimmed Hot - Orange]

[Dimmed Hot - Black]

Neutral

Neutral

Neutral

Neutral

Neutral

Neutral

Dimmed Hot

Dimmed Hot

Dimmed Hot

Dimmed Hot

Dimmed Hot

Dimmed Hot

Switched Hot

Switched Hot

Switched Hot

Switched Hot

Switched Hot

Switched Hot

Hot

Hot

Hot

Hot

Hot

Hot

Small Flatblade 

Screwdriver

Universal Source Controller

WaveLinx Wired

MN503104ML   

page 11

February 2021

www.cooperlighting.com

Summary of Contents for WaveLinx Wired SC-UN

Page 1: ...ly by a qualified electrician The installation must comply with the appropriate electrical codes and regulations in force in your area The Universal Source Controllers are designed for indoor installa...

Page 2: ...ibution to Circuits 10 Supply to Internal Circuitry 10 Load Wiring 10 High Voltage Load Wiring 10 Total Load Per Channel 11 Load Wire Gauges 11 Earth Connections 11 High Voltage Load Wiring Flows 11 T...

Page 3: ...N 1P ML 20 120 VAC 1 Phase 6 Main Lugs 16A per Channel SC120 12 UN 1P ML 20 12 SC120 06 UN 3P ML 20 3 Phase 6 SC120 12 UN 3P ML 20 12 SC120 24 UN 3P ML 20 24 SC277 06 UN 1P ML 20 277 VAC 1 Phase 6 SC2...

Page 4: ...in 517 mm 27 8 in 707 mm 0 89 in 22 5 mm 0 89 in 22 5 mm 0 98 in 25 mm 0 98 in 25 mm 4 53 in 115 mm 4 53 in 115 mm 1 1 in 28 mm 1 1 in 28 mm 1 1 in 28 mm 1 1 in 28 mm 1 1 in 28 mm 1 1 in 28 mm 13 76...

Page 5: ...cian The installation must comply with the appropriate electrical codes and regulations in force in your area The Universal Source Controllers are designed for indoor installation and use only The uni...

Page 6: ...the minimum distances to walls and other equipment shown in the diagrams below are maintained Also ensure that the stated ambient atmosphere requirements are not exceeded Refer to Important points fo...

Page 7: ...sufficient strength and quality to safely hold the unit ES C 1 2 0 EN T 3 4 5 6 7 8 9 1 2 in 30 mm 1 2 in 30 mm 1 2 in 30 mm 34 8 in 885 mm 54 32 in 1379 8 mm 54 32 in 1379 8 mm 13 4 in 340 mm 13 4 in...

Page 8: ...lace the two upper and two lower fixing screws Supply Wiring Wiring Flow The Universal Source Controller range has been designed to provide a clear layout and logical progression for all power circuit...

Page 9: ...uit 277V 2 0 AWG 70 mm2 2 0 AWG 70 mm2 2 AWG 35 mm2 SUPPLY EARTH HOT NEUTRAL Three Phase Supply The Universal Source Controllers are available in three phase supply variants ote N Check the stated vol...

Page 10: ...uitry The internal power supply that feeds the control panel and associated circuitry can draw its power from any and all phases so that it will still operate in the event that not all supply phases a...

Page 11: ...uits and couplers Please see the wiring flow diagram on page 8 Typical Load Connections The examples below show some of the most typical loads and the way in which they are connected to a Source Contr...

Page 12: ...0V 0V 0V 0V For each circuit the low voltage control protocol to be used is selected using the configuration menu on the control panel The programming of the Source Controller channels is covered with...

Page 13: ...w the control panel accessible either through a removable mini panel or when the complete casing is removed Termination The iCAN DMX and RS 485 are daisy chain protocols that all require termination o...

Page 14: ...tton for menu navigation Clear Text Display Link and Status Indicators Flashes Regularly to Indicate Correct System Operation When ON indicates that the timeclock function is enabled Where multiple SC...

Page 15: ...ss the ENT button Depending on the chosen option you will be able to affect outputs as follows All Channels Use the and buttons to adjust the output level 0 to 100 for all channels When the required o...

Page 16: ...ighlight the option that you wish to alter and then press the button to change its ON OFF status 3 Press the ENT button to save your changes and exit Changing the Operation Menu Password The unit uses...

Reviews: