Risk of Fire, Electrical Shock, Cuts or other Casualty Hazards- Installation and maintenance of this product must be 

performed by a qualified electrician. This product must be installed in accordance with the applicable installation code 

by a person familiar with the construction and operation of the product and hazards involved. For continued protection 

against shock hazard replace all covers and guards after field wiring is completed.

Risk of Fire and Electric Shock-

 Before installing or performing any service, the power MUST be turned OFF. 

 

All installations should be in compliance with the National Electric Code and all state and local codes.

Risk of Burn-

 Disconnect power and allow product to cool before handling or servicing.

Risk of Personal Injury-

 Due to sharp edges, handle with care.

Failure to comply with these instructions may result in death, serious bodily injury and property damage.

DISCLAIMER OF LIABILITY: 

Cooper Lighting Solutions assumes no liability for damages or losses of any kind that may arise  

from the improper, careless, or negligent installation, handling or use of this product.  

IMPORTANT: 

Read carefully before installing product. Retain for future reference.  

NOTICE: 

Product may become damaged and/or unstable if not installed properly. 

Note: 

Specifications and dimensions subject to change without notice.

ATTENTION Receiving Department: 

Note actual product description of any shortage or noticeable damage on delivery receipt.  

File claim for common carrier (LTL) directly with carrier. Claims for concealed damage must be filed within 15 days of delivery. 

 

All damaged material, complete with original packing must be retained.

NOTICE: 

All new wiring must be fully verified before applying power.

NOTICE: 

Designed for indoor installation and use only. Dry location rated.

Please Read This First

The Universal Source Controllers are designed, built and tested to strict safety regulations. By following the steps listed below and elsewhere within this 

guide, you can ensure safe installation and operation of these controller units.

 • The Universal Source Controllers must be installed only by a qualified electrician

 •

The installation must comply with the appropriate electrical codes and regulations in force in your area

 •

The Universal Source Controllers are designed for indoor installation and use only. The units can, however, be used to control appropriately certified 

exterior lighting fixtures

 •

Ensure that all wiring used conforms fully to local specifications and is sufficiently rated for the installation

 •

All new wiring must be fully verified before applying power

 •

The high voltage supply should be fed to the Universal Source Controller via an external isolation breaker with sufficient capacity for the planned 

installation

 •

All Universal Source Controllers exceed the weight limit for one person lifting - always use at least two people when lifting and mounting the units

 •

Do not mix load types within a single channel (e.g. 120V tungsten and low voltage ballast control)

 •

Ensure that the supply is fully isolated at an external breaker before removing the chassis covers. Test that power has been removed before starting 

to handle conductors

 •

Ensure that high voltage and low voltage wiring remains separate

Important Points For Consideration

 •

The Universal Source Controllers must be mounted flush with the wall, do not recess the controller chassis

 •

Upper and lower raceways must not be located within 8 inches (200 mm) of the upper and lower panels of the Universal Source Controller. Use 

suitable conduits and couplers to link the raceways to the controller chassis

 •

Allow adequate space for future maintenance of the unit. Do not install in a location that will later be difficult to access

 • The Universal Source Controllers are designed to be mounted vertically

 •

During operation, the Universal Source Controllers will produce audible noise caused by electrical noise suppression circuitry and also the circuit 

relays within the unit. The noise is a low level buzz that varies with the level of dimming and also clicks when relays are energised. Take these 

matters into consideration when deciding on a suitable mounting position.

 •

The hinged cover must be unscrewed and removed from the front cover when the Universal Source Controller operates at full load in a high ambient 

environment

Universal Source Controller

  WARNING

WaveLinx Wired

Installation Instructions 

Model # SC-UN

Summary of Contents for WaveLinx Wired SC-UN

Page 1: ...ly by a qualified electrician The installation must comply with the appropriate electrical codes and regulations in force in your area The Universal Source Controllers are designed for indoor installa...

Page 2: ...ibution to Circuits 10 Supply to Internal Circuitry 10 Load Wiring 10 High Voltage Load Wiring 10 Total Load Per Channel 11 Load Wire Gauges 11 Earth Connections 11 High Voltage Load Wiring Flows 11 T...

Page 3: ...N 1P ML 20 120 VAC 1 Phase 6 Main Lugs 16A per Channel SC120 12 UN 1P ML 20 12 SC120 06 UN 3P ML 20 3 Phase 6 SC120 12 UN 3P ML 20 12 SC120 24 UN 3P ML 20 24 SC277 06 UN 1P ML 20 277 VAC 1 Phase 6 SC2...

Page 4: ...in 517 mm 27 8 in 707 mm 0 89 in 22 5 mm 0 89 in 22 5 mm 0 98 in 25 mm 0 98 in 25 mm 4 53 in 115 mm 4 53 in 115 mm 1 1 in 28 mm 1 1 in 28 mm 1 1 in 28 mm 1 1 in 28 mm 1 1 in 28 mm 1 1 in 28 mm 13 76...

Page 5: ...cian The installation must comply with the appropriate electrical codes and regulations in force in your area The Universal Source Controllers are designed for indoor installation and use only The uni...

Page 6: ...the minimum distances to walls and other equipment shown in the diagrams below are maintained Also ensure that the stated ambient atmosphere requirements are not exceeded Refer to Important points fo...

Page 7: ...sufficient strength and quality to safely hold the unit ES C 1 2 0 EN T 3 4 5 6 7 8 9 1 2 in 30 mm 1 2 in 30 mm 1 2 in 30 mm 34 8 in 885 mm 54 32 in 1379 8 mm 54 32 in 1379 8 mm 13 4 in 340 mm 13 4 in...

Page 8: ...lace the two upper and two lower fixing screws Supply Wiring Wiring Flow The Universal Source Controller range has been designed to provide a clear layout and logical progression for all power circuit...

Page 9: ...uit 277V 2 0 AWG 70 mm2 2 0 AWG 70 mm2 2 AWG 35 mm2 SUPPLY EARTH HOT NEUTRAL Three Phase Supply The Universal Source Controllers are available in three phase supply variants ote N Check the stated vol...

Page 10: ...uitry The internal power supply that feeds the control panel and associated circuitry can draw its power from any and all phases so that it will still operate in the event that not all supply phases a...

Page 11: ...uits and couplers Please see the wiring flow diagram on page 8 Typical Load Connections The examples below show some of the most typical loads and the way in which they are connected to a Source Contr...

Page 12: ...0V 0V 0V 0V For each circuit the low voltage control protocol to be used is selected using the configuration menu on the control panel The programming of the Source Controller channels is covered with...

Page 13: ...w the control panel accessible either through a removable mini panel or when the complete casing is removed Termination The iCAN DMX and RS 485 are daisy chain protocols that all require termination o...