M-LIB3 Low Impedance Bus Differential Relay
22
6.1 GENERAL CHARACTERISTIC
Currents from the CTs of the Feeders connected to each protected zone are conveyed to a wiring bus
(one for each phase) that drives the positive and negative halfwave of the current on two different wires.
The wiring bus also carries the signal from the CT’s saturation detectors.
One M-LID3 differential relay is connected to the wiring bus of its protected zone and from the wiring bus of each
phase it can measure :
q
The bias current I
R
proportional to the arithmetic summation of all the incoming and outgoing currents of the
feeder connected to the protected busbar zone.
q
The differential current I
d
proportional to the vector summation of all the currents of the zone.
The CTs saturation detectors shunt the measurement of I
d
during saturation due to faults external to the protected
zone.
The I
d
measuring circuits are transformer isolated whereas the I
R
measuring circuits are optoisolated.
6.2 POWER SUPPLY
The auxiliary power is supplied by a fully isolated and self protected, built-in, interchangeable module.
Two options are available
:
24V(-20%) / 110V(+15%) a.c.
80V(-20%) / 220V(+15%) a.c.
a) -
b) -
24V(-20%) / 125V(+20%) d.c.
90V(-20%) / 250V(+20%) d.c.
Before energizing the unit check that supply voltage is within the allowed limits.
6.3 MEASUREMENTS ACQUISITION AND OPERATION PRINCIPLE
For enhanced reliability the A/D converters and the signal measuring circuits are totally duplicated.
Furthermore all the signal-processing elements are duplicated.
It means that any step of operation takes place only if two elements produce the same output.
The basic detection elements are :
q
The CTs Circuit Supervision element which compares the actual differential current I
d
with the CTs Circuit
Supervision Level I
SV
:
operation when I
d
> [I
SV
]
q
The zone differential current element which compares the actual differential current I
d
with the set minimum
pick-up level I
dS
:
operation when I
d
> [I
dS
]
q
The zone Biased Differential Current element which compares the actual differential current with the actual
trip level “I
S
” calculated in function of the zone through current I
R
and the bias coefficient R
operation when Id> ([I
dS
] + R
•
I
R
)
Summary of Contents for Low Impedance Bus Differential Relay M-LIB3
Page 12: ...M LIB3 Low Impedance Bus Differential Relay 12 3 1 SINGLE LINE DIAGRAM SINGLE LINE DIAGRAM...
Page 14: ...M LIB3 Low Impedance Bus Differential Relay 14...
Page 17: ...S150 34 1 17 4 1 WIRING DIAGRAM M BF3 SCE1577...
Page 20: ...M LIB3 Low Impedance Bus Differential Relay 20 5 1 WIRING DIAGRAM M BC3 SCE1578...
Page 34: ...M LIB3 Low Impedance Bus Differential Relay 34 6 19 WIRNG DIAGRAM M LID3 SCE1579...
Page 36: ...M LIB3 Low Impedance Bus Differential Relay 36 This page intentianally left blank...