6.14 READING OF PROGRAMMED SETTINGS AND RELAY'S CONFIGURATION
Enter the mode "SET DISP", select the menu "SETTINGS" or "F
→
RELAY", scroll information available in the
menu by keys "+" or "-".
SETTINGS= values of relay's operation parameters as programmed
F
→
RELAY= output relays associated to the different functions as programmed.
6.15 PROGRAMMING
The relay is supplied with the standard default programming used for factory test. [ Values here below reported
( ----- )
].
All parameters can be modified as needed in the mode PROG and displayed in the mode SET DISP
Programming is enabled only if no input current is detected (main circuit breakers open).
As soon as programming is enabled, the LED PRG/IRF flashes and the reclosing lockout relay R5 is de-
energized. Enter MODE "PROG" and SELECT either "SETTINGS" for programming of parameters or
"F
→
RELAY" for programming of output relays configuration; enable programming by the indirect operation key
PROG.
The key SELECT now scrolls the available parameters. By the key (+) , (-) the displayed values can be
modified; to speed up parameter's variation press the key SELECT while "+" or "-" are pressed.
Press key "ENTER/RESET" to validate the set values.
6.15.1 PROGRAMMING OF FUNCTIONS SETTINGS
Mode PROG menu SETTINGS. (Production standard settings here under shown).
Display
Description
Setting Range
Step
Units
xxxxxxx
Current date
DDMMMYY
-
-
xx:xx:xx
Current time
HH:MM:SS
-
-
Fn
50
Hz
System frequency
50 - 60
10
Hz
Ids
0.2
In
Basic minimum pick-up level of differential element
0.2 – 2 – Dis
0.01
In
trf
1
s
Trip time delay of the Relay’s Internal Fault Detector
0.1 – 9.9
0.1
s
BI
OFF
Blocking Input enable
OFF – ON
-
-
1R
0.5
pu
Bias coefficient in the zone [1I
R
] <I
R
< [2I
R
]
0.4 – 1
0.01
pu
1IR
1
In
Action starting level for 1R
0.5 – 2.0
0.1
In
2R
1.0
pu
Bias coefficient in the zone I
R
> [2I
R
]
0.4 – 1.00
0.01
pu
2IR
6
In
Action starting level for 2R
3 – 8
0.1
In
Isv
0.2
In
Minimum pick-up level of CT supervision element
0.1 – 1 - Dis
0.01
In
tsv
1
s
Time delay of the C.T Supervision element
0.1 – 9.9
0.1
s
TRG:
Ext
Trigger for oscillography records is Internal or External
(via digital input B3)
Ext - Ids
Is – Isv
-
-
Tsyn
Dis
m
Synchronization time internal
5-10-15
30-60-Dis
-
-
NodAd
1
Identification number for connection on serial
communication bus
1 - 250
1
-
The setting Dis indicates that the function is disabled.
In
500
Ap
In
is the unit of
measure,
0.2
is the
setting
default
Ids
is the
name
of the variable
Summary of Contents for Low Impedance Bus Differential Relay M-LIB3
Page 12: ...M LIB3 Low Impedance Bus Differential Relay 12 3 1 SINGLE LINE DIAGRAM SINGLE LINE DIAGRAM...
Page 14: ...M LIB3 Low Impedance Bus Differential Relay 14...
Page 17: ...S150 34 1 17 4 1 WIRING DIAGRAM M BF3 SCE1577...
Page 20: ...M LIB3 Low Impedance Bus Differential Relay 20 5 1 WIRING DIAGRAM M BC3 SCE1578...
Page 34: ...M LIB3 Low Impedance Bus Differential Relay 34 6 19 WIRNG DIAGRAM M LID3 SCE1579...
Page 36: ...M LIB3 Low Impedance Bus Differential Relay 36 This page intentianally left blank...