background image

4

Instructional Leaflet

LCR 6200 Load Control Receiver

Commissioning the ZigBee Module

Perform the following steps to commission the 
ZigBee communication module in the LCR 6200:

1. Make sure a ZigBee Gateway device has been 

previously installed and commissioned.

2. Locate and record the serial number of the 

ZigBee Gateway device.

3. Coordinate with the Yukon™ Master Station 

operator to create an LCR 6200 using the 
Install Code and EUI-64 address of the LCR, 
which were recorded in 

step 4 on page 3

.

NOTE 

The Install Code and EUI-64 address are 

located on labels inside the LCR.

4. Instruct the Yukon Master Station operator to 

assign the LCR 6200 to the ZigBee Gateway 
device with the serial number recorded in 

step 

2

.

5. Instruct the Yukon Master Station operator to 

start the commissioning process by clicking 
the Commission button located on the 
hardware page of the LCR 6200 that was 
created in 

step 3

.

6. Push and hold the Test button on the LCR 

receiver board for more than five seconds to 
instruct the ZigBee module to join the ZigBee 
network.

NOTE 

The commissioning process may take up to 

five minutes to complete. When the 
commissioning process is complete, the LCR 
Status LCD turns on solid and the ZigBee 
status of the LCR changes to Commissioned 
in the Yukon software.

LCR 6200 LEDs

The LCR 6200 LEDs have the following meanings:

Load Status (Red)

LED Off

 – LED is off when the load is not being 

controlled.

LED On

 – LED is on when the load is being 

controlled.

LCR Status (Green)

LED Off

 – LED is off when there is no 

communication, the LCR is out of service, or the 
LCR status LED is disabled.

LED On

 – LED is on solid when the ZigBee module 

is connected to a network.

LED Fast Blink

 – LED blinks with a pattern of half 

a second on and half a second off when the 
ZigBee module is in the process of 
commissioning.

LED Very Fast Blink

 – LED blinks very fast when 

the ZigBee module is scanning for a network.

LED Slow Blink

 – LED blinks with a pattern of one 

second on and one second off if the ZigBee 
module did not find a network or the ZigBee 
module left a network and did not rejoin that 
network.

Summary of Contents for LCR 6200

Page 1: ...sent through the SelectComm and ZigBee communication modules No special test equipment or programming is required to install the LCR 6200 in the field The LCR 6200 addressing must be configured for your demand response system prior to operation CAUTION Observe precautions for handling electrostatic sensitive devices MISE EN GARDE Respectez les précautions de manipulation des dispositifs à décharge...

Page 2: ...ated throughout the document SAFETY FOR LIFE SAFETY FOR LIFE Hazard Statement Definitions This document may contain four types of hazard statements DANGER Indicates a hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not...

Page 3: ...the wiring within a 1 2 liquid tight non metallic flexible conduit or make sure the wiring is close nippled into an approved junction box or wiring compartment All wiring connections are made to factory installed leads that are rated for 600 VAC 105 C No polarity requirements apply to the output leads 4 Locate and record the LCR address Install Code EUI 64 address and any other necessary informati...

Page 4: ...he LCR receiver board for more than five seconds to instruct the ZigBee module to join the ZigBee network NOTE The commissioning process may take up to five minutes to complete When the commissioning process is complete the LCR Status LCD turns on solid and the ZigBee status of the LCR changes to Commissioned in the Yukon software LCR 6200 LEDs The LCR 6200 LEDs have the following meanings Load St...

Page 5: ...to increment the control time by the configurable period of time For example if the configurable period of time is set to 30 seconds push the Test button four times to control for two minutes The relay control initiated by the Test button is implemented as a standard timed load control command zero delay and zero random extension This overrides any other currently implemented or delayed control Wh...

Page 6: ...12 1 IEC 61000 4 2 Surge Withstand Capability Oscillatory 6 kV 100 kHz waveform per ANSI C12 1 IEEE C62 41 Fast Transient 6 kV 1 2x50 μs 8x20 μs waveform per ANSI C12 1 IEEE C62 41 Wire Size Limits This energy management device is designed tested and certified to UL Standard 916 which contains allowances for field wiring system conductor sizing It is intended to be connected directly to the equipm...

Page 7: ...Cooper Power Systems 7 CT Y0 0398 SAFETY FOR LIFE ...

Page 8: ...scriptions or safety notations LCR 6200 Load Control Receiver FCC COMPLIANCE STATEMENT This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation This equipment has been tested and found to co...

Reviews: