7
Cooper Lighting Solutions
Installation instructions
Digital Wall Switch Timer
INSTALLATION
CAUTION:
BEFORE WIRING AND SERVICING, POWER TO THIS TIME
SWITCH AND THE EQUIPMENT IN CONTROLS MUST BE
TURNED OFF AT THE MAIN PANEL.
WARING:
UNIT MUST
BE PROPERLY GROUNDED TO OPERATE CORRECTLY.
1. Connect the wires as shown in the single pole wiring
diagram.
2. Cap the unused ground wire.
3. Mount the timer inside the electrical box using the 2
mounting screws provided.
4. Install the enclosed cover plate.
5. Turn the power ON at the electrical panel.
6. When powering up for the first time, allow 1 minute for
the unit to show OFF on the screen.
• An LCD “OFF” message will be displayed as a default
and the load will be switched OFF.
DESCRIPTION OF OPERATION
The solid state interval timer is designed to control lighting
and motor loads. Momentarily pressing the start/stop but-
ton located on the front of the unit will turn the load ON and
start the count-down time (set by the user utilizing the DIP
Switches) at the end of which the load will turn OFF. If there
is a need to turn the load OFF before the count-down time
has expired, press the start/stop button momentarily. The
unit can be programmed via DIP switch settings to flicker
the load (lights), and/or beep as a warning indicating that
the load is about to turn OFF. A scroll option can be set to
temporarily change the preset count-down time by pressing
and holding down the start/stop button for more than 3
seconds.
FEATURES
•
LCD display that stands out strongly in lighted areas
and is backlit for visibility in dark areas.
• Tamper resistant time-on interval, which can be preset.
In addition, a manual scroll-up mode that can override
the setting temporarily – this feature can be disabled,
thereby providing a fixed interval timer.
•
Flicker of lights and/or beep warning, which begins 2
minutes before time-out (either or both can be disabled).
•
Zero power switching to prolong the life of relay
contacts by switching high inrush equipment at or close to
zero power.
•
Incandescent lighting, or motor loads, compatible with
electronic ballasts.
•
Decorator typeface with matching wallplate included.
RATINGS
CONTACT RATING:
TYPE OF LOAD
T
120VAC
ext
277VAC
Resistive
15A
15A
Ballast
10A
10A
LED Driver
1200W
1200W
Tungsten
960W
-
Motor
1/2 HP
-
Pilot Duty
360VA
-
Note:
No minimum load requirement.
Dual Voltage Input:
120/277 VAC (No Minimum Load)
• Maximum Load: 960Watts, 10 amps @ 120 VAC
• Maximum Load: 1200Watts, 10 amps @ 277 VAC
Environment:
• Operating Temperature: 0-100°F
• Operating Humidity: 90% RH non-condensing