Installation Instructions – Galleon II Area Site and Flood 

6

Cooper Lighting Solutions    

   

IB500157EN

 

    

 Installation instructions

Figure 10.   

Customer 

Pole

3/8-16 

Flange Bolt

Bracket Arm

M Pattern Nut 

Plate

#8 Screw

Access Door

Access Cover

Lock Tabs

Swept Arm

2X - 1/2-13 Flange Bolts

Figure 9.   

Upswept Arm (UP) (Fig. 9)

Tools Required:

• 

Ratchet with 9/16” and 3/4" sockets

• 

#2 Phillips head screwdriver

1.  Remove the pole top cap.

2.  Loosen (1) #8 screw to remove the access cover from 

the arm. Rotate down, sliding the cover rearward to 

disengage from the front slots.

3.  Install and hold the provided nut plate inside the pole. 

Install (1) 1/2"-13 fastener through the adapter, pole and 

into the nut plate, and hand-tighten. Insert the lower 

1/2"-13 fastener, keeping loose to ensure alignment 

while tightening the upper mount. Tighten the upper 

flange bolt to arm bracket and pole to 40 ft-lbs.    

(54 N-m.)

4.  Remove the lower 1/2"-13 fastener and position fixture 

over adapter bracket. The quick mount arm will engage 

the slot on the adapter bracket to secure the fixture. 

With the fixture supported, reinstall the lower 1/2"-13 

fasteners and hand-tighten.

5.  Install the 3/8”-16 fastener through the arm bracket 

into the arm. Hand-tighten to ensure alignment, then 

tighten the ½”-13 lower flange bolt to 40 ft-lbs. (54 

N-m.) Tighten the 3/8”-16 upper flange bolt to 20 ft-lbs. 

(27 N-m.). 

6.  Route the fixture leads through the center opening of 

the nut plate, pole and arm into the arm cavity.

7.  Attach the supply side ground wire to the ground 

terminal connector (green wires).

8.  Connect the supply side line voltage wire to the fixture 

side line voltage terminal connector (black wires).

9.  Connect the supply side neutral wire to the fixture side 

neutral wire terminal connector (white wires).

10.  Insert the access cover by inserting the tabs into the 

front arm slots. Tighten the (1) #8 screw to 14 in-lbs.

11.  Replace pole top cap.

Photocontrol Orientation (If Equipped – Fig 10.)

ote: 

N

If your luminaire is equipped with a photocontrol 

receptacle, see IB525002EN Photocontrol 

Receptacle Supplement to identify your photocontrol 

and follow the instructions on the diagram and all 

applicable notes

Bi-Level Switching (If Equipped)

For Bi-level switching, the input leads to the fixture will be 

independently labeled to indicate dimming preferences as 

appropriate (as defined by the order requirements). Two 

separate supply lines of line voltage, neutral and ground 

must be connected to the fixture leads to enable the bi-level 

switching functionality of the fixture.

Maintenance

A regular maintenance schedule should be followed to 

retain optimal light output and thermal performance. Optical 

lens cleaning should be performed with a clean dry cloth to 

remove any dust or other contaminants. Additional cleaning 

can be performed with non-abrasive acrylic cleansing 

solution.

Photocell Receptacle

Summary of Contents for Galleon II

Page 1: ...ure to rain dust or other environmental conditions prior to installation and insertion of photo control or shorting cap if so equipped Best results will be obtained if installed and maintained accordi...

Page 2: ...wn sliding the cover forward to disengage from the rear slots 3 Thread 1 1 2 13 fastener through the top hole of the quick mount adapter bracket through the top hole on the pole and into the nut plate...

Page 3: ...late Center Wire Way Round Pole Adapter 2X 1 2 13 Flange Bolt 2X Adjustment Bolt Do Not Remove Access Cover 3X 8 Screw Washer Plate Ensure B Arrow Is Facing Down Figure 3 Wall Mount Fixed WM Fig 4 Too...

Page 4: ...to remove the access cover from the arm Set aside for installation 2 Align the center holes in the decorative wall plate to the fixture arm Install the washer plate and the 2 13 fasteners and hand ti...

Page 5: ...crews then tighten the upper angled set screws to 20 ft lbs Install 3 hex nuts to the lower set screws and tighten both the 3 set screws and 3 nuts to 20 ft lbs 5 Inside the slipfitter arm connect sup...

Page 6: ...lt to 20 ft lbs 27 N m 6 Route the fixture leads through the center opening of the nut plate pole and arm into the arm cavity 7 Attach the supply side ground wire to the ground terminal connector gree...

Page 7: ...ion lectrique est HORS TENSION avant de commencer l installation ou de tenter d en faire l entretien Mettez l alimentation lectrique hors tension depuis le fusible ou le disjoncteur Risque d incendie...

Page 8: ...19 16 po et 1 9 cm 3 4 po Tournevis pointe cruciforme n 2 1 Assurez vous que le poteau est perc pour un motif de type N et retirez le couvercle sup rieur du poteau 2 Desserrez les deux 2 vis n 8 pour...

Page 9: ...blanc du luminaire c Le fil de tension provenant de l alimentation avec le fil noir du luminaire 9 Desserrez les deux 2 boulons embase M20x1 5 3 8 po 16 situ s dans les fentes pour r gler les angles d...

Page 10: ...et la fl che soient orient s vers le bas 3 Serrez les deux 2 fixations M14x2 1 2 po 13 un couple de 54 Nm 40 pi lb Mettez le luminaire de c t 4 Faites passer les fils d alimentation de la bo te de jon...

Page 11: ...M10x1 5 3 8 16 5X crous embase Poteau du client CROSSE Adaptateur d embo tement r glable Fig 7 et 8 Outils requis Cl rochet avec douille de 1 9 cm 9 16 po Cl hexagonale de 0 5 cm 1 4 po Cl de 1 9 cm 3...

Page 12: ...rer pour assurer l alignement tout en serrant le support de montage sup rieur Serrez le boulon embase sup rieur au support du bras et au poteau un couple de 54 Nm 40 pi lb 4 Retirez la fixation inf ri...

Page 13: ...u et toutes les remarques applicables Commutateur deux niveaux d intensit selon l quipement En cas de commutation deux niveaux d intensit chaque fil d alimentation du luminaire comportera une tiquette...

Page 14: ...nstalaci n o intentar realizar cualquier tipo de mantenimiento Desconecte la alimentaci n el ctrica en el fusible o cortacircuitos Riesgo de incendio consulte la etiqueta del producto para conocer los...

Page 15: ...del poste 2 Afloje los 2 tornillos n 8 para retirar la cubierta de acceso del brazo Gire hacia abajo deslizando la cubierta hacia adelante para que se suelte de las ranuras traseras 3 Enrosque 1 suje...

Page 16: ...voltaje de l nea del lado de la alimentaci n al terminal negro de la luminaria 9 Afloje los 2 pernos de 3 8 16 ubicados en las ranuras para hacer ajustes de ngulo a la luminaria Una vez realizados es...

Page 17: ...a B y la flecha miren hacia abajo 3 Apriete los 2 tornillos de 1 2 13 a 40 pies lb 54 Nm Deje a un lado la unidad de la luminaria 4 Tienda los cables de alimentaci n desde la caja de derivaci n a trav...

Page 18: ...da ar los cables dentro del brazo del m stil Este orificio se puede perforar previamente para evitar da os en los cables 7 Instale el perno pasante de 3 8 16 x 4 5 y apriete a 14 pies lb 18 Nm 1 aran...

Page 19: ...las ranuras delanteras 3 Instale y sostenga la placa de tuerca provista dentro del poste Instale 1 sujetador de 1 2 13 a trav s del adaptador el poste y en la placa de tuerca y aj stelo a mano Inserte...

Page 20: ...si est provisto Para contar con un interruptor de doble nivel los cables de entrada a la luminaria deber n etiquetarse por separado para indicar las preferencias de regulaci n seg n corresponda defin...

Page 21: ...ent generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of th...

Reviews: