Types VXE15 and VXE27
Electronically Controlled Single-Phase;
Installation and Operation Instructions

Reclosers

Service Information

S280-16-1

Printed in USA

November 2002 • Supersedes 8/01

Figure 1.
Kyle

®

Type VXE electronically controlled, single-phase, vacuum-interrupting automatic circuit recloser. 

020100KM

VXE15 Serial Number 11009 and above
VXE27 Serial Number 1948 and above

VXE Control Serial Number 7401 and above

Safety Information 

......................................................

2

Safety Instructions  ....................................................

2

Hazard Statement Definitions ...................................

2

Product Information 

....................................................

3

Introduction ...............................................................

3

Acceptance and Initial Inspection .............................

3

Handling and Storage ...............................................

3

Description ................................................................

3

Manual Operating Levers and Indicators  .................

5

Recloser Data Plates ................................................

6

Control Programming and Operation 

.......................

7

Type VXE Electronic Control  ....................................

7

Programming the Control Settings  ...........................

8

Specifications and Ratings 

......................................

10

Dimensions 

................................................................

11

Installation Procedure 

..............................................

12

Placing the Recloser In Service  .............................

13

Operation 

...................................................................

14

Manual Operation of Energized Recloser  ..............

14

Non-Reclosing Operation  .......................................

14

Automatic Operation ...............................................

14

Lockout Indication ...................................................

14

Testing 

.......................................................................

15

Safety Requirements  ..............................................

15

Test Equipment Required  .......................................

15

Manual Closing Procedure  .....................................

16

High-Potential Insulation Withstand Tests  ..............

16

Minimum-Trip Current Level Test  ...........................

17

Sequence of Operation Test  ...................................

17

Electrical Operation of Closing Solenoid Test  ........

18

Accessories 

...............................................................

19

Extra Creepage Bushings  ......................................

19

Bushing-Type Multi-Ratio Current Transformer ......

19

Low-Voltage Closing ...............................................

19

Cable-Locking Sleeve .............................................

19

SCADA Input/Output Board  ....................................

19

Maintenance Information 

.........................................

20

Contents

NOTICE: This bulletin is also applicable to Kyle product
serial numbers beginning with the prefix CP57.

Summary of Contents for VXE Control

Page 1: ...rogramming and Operation 7 Type VXE Electronic Control 7 Programming the Control Settings 8 Specifications and Ratings 10 Dimensions 11 Installation Procedure 12 Placing the Recloser In Service 13 Ope...

Page 2: ...ting main taining or testing this equipment carefully read and understand the contents of this manual Improper operation handling or maintenance can result in death severe personal injury and equipmen...

Page 3: ...ss is discov ered file a claim with the carrier immediately Check for oil leakage and tighten all bolts that may have loosened during shipment especially the tank mounting bolts Tank mounting bolts sh...

Page 4: ...voltage closing is sup plied through a 2 pin connector mounted on the recloser head Closing Solenoid Operation The closing operation is illustrated by considering the recloser to be connected to the l...

Page 5: ...ion the lever is pulled from under the sleet hood to its down position as shown in Figure 2 The lever must be manually returned to the up position in order to return the recloser to its pre programmed...

Page 6: ...eration section of this manual for further information The VXE control can be equipped with an optional SCADA input output board to provide remote operation and status functions for SCADA applications...

Page 7: ...pening actuator In addition a control battery is required to supply power to the control during the reclose intevals If line current drops below 3 A or the recloser is in the open position power is th...

Page 8: ...le protecting fuses from tem porary faults Sequence Coordination is always active for the number of TCC1 operations selected for the VXE control For example for two trip operations on TCC1 and two tri...

Page 9: ...TCC2 Time Current Curve Modifiers The DIP switches labeled S6 Figure 5 are used to mod ify the shape of the time current curve produced by the TCC plug in card for TCC1 and or TCC2 Each TCC plug in ca...

Page 10: ...imate inches 0 4 0 5 Contact Close Time Close Signal To Contact Make seconds 0 19 0 24 Open Contact Travel Time Open Signal To Contact Part seconds 0 014 0 022 Interrupting Time Open Signal to Arc Ext...

Page 11: ...Pole Bolt Connector NO 6 350 MCM 16 UNC 2B 8 5 Figure 6 Dimensions of Types VXE15 and VXE27 reclosers Type Bushing Type A B C VXE15 standard 1156 45 5 483 19 270 10 5 VXE15 extra creepage 1237 48 75 5...

Page 12: ...ug as shown in Figure 4 Make sure that all DIP switch settings are set correctly and that the control cable is connected between the recloser and control 6 Mount the recloser Use the lifting lug locat...

Page 13: ...en placing the recloser in service Be sure that the control battery is properly connected When the recloser is connected and source side high voltage lines are energized by closing the source side dis...

Page 14: ...dle down and returning the yellow handle to its up Closed position If the VXE con trol is equipped with the optional SCADA input output accessory board the recloser can be remotely closed from lockout...

Page 15: ...n the 600 5 tap 3 Ammeter Must have a rating based on the level of test current Since the control is responsive to peak current it is recommended that metering responsive to peak current be used when...

Page 16: ...the pipe plug in the head casting before placing the recloser in service High Potential Insulation Level Withstand Tests High potential withstand tests provide information on the dielectric condition...

Page 17: ...when the recloser trips and compare to the VXE control s pro grammed minimum trip value Sequence of Operation Test The operating sequence can be checked by using the manual closing tool to close the r...

Page 18: ...ating correct operation of the clos ing solenoid Type VXE Single Phase Electronically Controlled Recloser Installation and Operation Instructions 18 Figure 13 Suggested test diagram for high voltage c...

Page 19: ...SCADA I O board also includes dry contacts to provide remote status information All remote features are accessed through a 19 pin recep tacle Type MS 22 14 female mounted on the bottom of the control...

Page 20: ...Department offers recloser mainte nance training classes These classes taught by experi enced service technicians are held at the factory s in house training facility For additional information contac...