Figure 19.
Form 3 electronic control tie board and control back panel. The test points listed above will be covered in detail in the "Detailed
Circuit Check" section of this manual.
Type ME Electronic Recloser Control
14
CAUTION:
Be sure that test equipment leads
have insulated clips to prevent short circuiting adja-
cent ME control terminals during testing. Shorting termi-
nals may cause permanent damage to circuit compo-
nents. The control may be inoperative and possible
misoperation (unintentional operation) of the recloser
may result.
!
82047KMA
Pre-Check
When troubleshooting a control reported to have failed or to
have not worked properly, always check for simple problems
first.
Detailed Circuit Checks
The following test procedures require only the following two
test devices.
A volt-ohm meter will be required (minimum meter input
impedance 20,000 ohms per volt) to perform tests.
The Kyle Type MET test set, or an actual recloser with a
source of primary or secondary test currents can also be used to
perform tests.