COOPER LIGHTING SOLUTIONS
IB519088EN Installation Instructions
Figure 1. Flat Unit
Figure 2. Shallow Cast
Figure 3.
Installation Instructions – B95 LED
INSTALLATION INSTRUCTIONS
Identify what type of unit is being installed. This will aid you through the remaining installation instructions. Refer to each
section for each specific type of unit. There are two styles of units (flat and shallow cast) as described by their depth of
protrusion from the mounting surface (see figures below). Begin by removing lens assembly using a Torx T20 screwdriver
for screws with center pin. (Screwdriver sold separately,
Cooper Lighting Solutions
catalog number VRSD or 1/4” bit VRSB).
ote:
N
These instructions do not claim to cover all details or
variations in the equipment, procedure, or process
described, or to provide directions for meeting every
possible contingency during installation, operation
or maintenance. When additional information is
desired to satisfy a problem not covered sufficiently
for user’s purpose, please contact your nearest
representative. Design specifications and dimensions
are subject to change without notice.
FLAT UNIT INSTALLATION:
1.
Remove lens, using a TORX T20 center pin reject
screwdriver.
2. Select the correct type fasteners to use for the
mounting surface, 1/4” nominal diameter (not supplied).
3. Center mounting plate on flat smooth ceiling or wall
over junction box. Use mounting plate as a template to
layout fastener locations. (See Figure 4).
4. Connect fixture wires to the proper supply wires and
place in junction box. Minimum 90°C supply wire
required. Ground fixture with wire provided.
Caution: Do not touch LEDs on fixture; care must be
taken to not come in contact with LED board(s) or
connector(s) during fixture installation.
5. Align fixture without lens to four mount holes. Make
sure connector on LED board is oriented at bottom
position for vertical mount fixture, or reflector is at top
position for horizontal mount fixture. Tighten all four
mounting fasteners sufficiently to compress back plate
into gasket.
Figure 4.
4.51in
6.18in
Lens
Backplate
Gasket
‘O‘- Ring
Lens Mounting Screw
Clearance Hole For 1/4’’ Bolt (4X)
Back Plate
Wall Or Ceiling
Junction Box