Figure 3
3.
To make final vertical adjustment, loosen the pivot bolts on the floodlight yoke to position floodlight
at the desired angle (limited to 60 degrees forward and 45 degrees back).
4. Rotate the floodlight housing to the desired position.
5. Tighten the two 1/2”-13 bolts to 45 ft-lbs (61.0 N-m). Tighten the 5/16”-18 bolts in the adjustment
slots to 12 ft-lbs (16.3 N-m).
6. Turn power on.
MAIntEnAncE
•
Perform visual, electrical, and mechanical inspections on a regular basis. The
environment and frequency of use should determine this. However, it is recommended
that checks be made at least once a year. We recommend an Electrical Preventive
Maintenance Program as described in the National Fire Protection Association Bulletin
NFPA 70B: Recommended Practice for Electrical Equipment Maintenance (www.nfpa.org).
•
The lens should be cleaned periodically to ensure continued lighting performance. To
clean, wipe the lens with a clean damp cloth. If this is not sufficient, use a mild soap or
a liquid cleaner. Do not use an abrasive, strong alkaline, or acid cleaner. Damage may
result.
•
Visually check for undue heating evidenced by discoloration of wires or other components,
damaged parts, or leakage evidenced by water or corrosion in the interior. Replace all
worn, damaged, or malfunctioning components and clean gasket seals before putting the
luminaire back into service.
•
Electrically check to make sure that all connections are clean and tight.
•
Mechanically check that all parts are properly assembled.
REPLAcEMEnt PARtS
Cooper Crouse-Hinds Pro-Flood LED Floodlights are designed to provide years of reliable lighting
performance. However, should the need for replacement parts arise, they are available through
your authorized Cooper Crouse-Hinds distributor. Assistance may also be obtained through your
local Cooper Crouse-Hinds representative or the Cooper Crouse-Hinds Sales Service Department,
P.O. Box 4999, Syracuse, New York 13221, Phone 866-764-5454.
DIMEnSIonS
532.9
21.0
405.9
16.0
525.6
20.7
203.7
8.0
277
10.9
234.5
9.2
552.5
21.75
.55
120.7
4.75
IF 1664 • 05/13
Copyright © 2013, Cooper Industries, Inc. Page 2
Figure 4
60°
45°
105°
45° PAST
VERTICAL
60° BEFORE
VERTICAL
AIMING RANGE
2.
Re-install the back panel and tighten all eight (8) panel mounting screws to 80 in-lbs (9.0 N-m).