6.4 LAMP INSTALLATION & REPLACEMENT (CONTINUED)

4. Remove lamp.

5. Perform cleaning and inspection as noted in the MAINTENANCE section.

6. Screw new lamp into lampholder and securely tighten lamp.  New lamp must

be identical type, size, and wattage as marked on the floodlight nameplate.

The lamp must be screwed tightly into the lamp holder.  Ensure that it is
screwed in fully so that no arcs or other inadmissible operating conditions
can occur.  Protect lamp from glass breakage during installation.

7. Thoroughly clean lens and cover gasket seal with a clean, damp cloth.  If this is

not sufficient, use a mild soap or a liquid cleaner such as Collinite NCF or Duco
#7.  Do not use an abrasive, strong alkaline, or acid cleaner.  Damage may
result.  

8. Close floodlight cover door making sure that all wires are safely inside and

positioned away from the ballast area.  Securely tighten all cover screws.  For
proper gasket seal, torque the cover screws to 10-14 lbs.-in. (1.13-1.58 Nm).

Over-tightening can impair the degree of protection.

6.5 PUTTING INTO OPERATION

Prior to taking the apparatus into operation, the tests specified in the relevant
national regulations shall be carried out.  Apart from that, the correct functioning
and installation of the apparatus in accordance with these operating instructions
and other applicable regulations must be observed.

Insulation measurements may only be carried out between PE and the external
conductor • L1 (L2, L3) as well as between PE and N.
- Measurement voltage:  max. 1 kVAC/DC
- Measurement current:  max. 10 mA
- The floodlight may only be operated when sealed.
- Carry out test in accordance with IEC 60079-15 33.7.1 (see Section 7.1).

7. MAINTENANCE/SERVICING

The relevant national regulations which apply to the maintenance/servicing of
electrical apparatus in explosive atmospheres shall be observed (IEC 60079-19).
Servicing:
When servicing, in particular those components that affect the explosion
protection, will have to be checked, e.g.:
- Housing for any cracks or damages.
- Gaskets for their perfect condition.
- Terminals and blanking plugs for their firm fit.
- Defective lamps must be replaced immediately.

The interval between maintenance depends upon the ambient conditions and the
hours of operation.  The suggested interval between lamp changes given by the
lamp manufacturer should be followed.  A visual check and the test to IEC 60079-
15 33.7.1 (see Section 6.1) should be carried out every 6 months.

We recommend a regular maintenance according to an approved preventive
maintenance program.  To prevent additional lumen depreciation, thoroughly clean
the lens and cover gasket seal with a clean, damp cloth.  If this is not sufficient,

use a mild soap or a liquid cleaner such as Collinite NCP or Duco #7.  Do not use
an abrasive, strong alkaline, or acid cleaner.  Damage may result.

7.1 TEST FOR RESTRICTED BREATHING TO IEC 60079-15
33.7.1:

This test is to be carried out:
- Installation
- Lamp change
- During scheduled maintenance
- Check the lamp holder for damage
- The lamp must be screwed tightly in to the lamp holder
- Tighten all cover screws (over-tightening of the screws can damage the threads)
- Connect test unit to the test point on the luminaire.  See Figure 7.
- The time required for a vacuum from 300 Pa (30mm water pressure) to reduce to
150 Pa (15mm water pressure) at constant temperature conditions, may not be
less than 80 sec. (see Figure 7).  If the vacuum cannot be maintained for this
length of time, then the seals (enclosure, cable entry, etc.) must be replaced.  After
this, the test must be repeated.

8. REPAIR/OVERHAUL/ MODIFICATIONS

Repairs and overhaul may only be carried out with genuine COOPER CROUSE-
HINDS spare parts.  Before lamp change or dismantling of individual parts, ensure
that no explosive atmosphere is present.  Switch off the apparatus before opening
or isolate before commencing maintenance.  Only use original spare parts.  If the
floodlight was previously in operation, then wait 15 minutes before opening.
Repairs that affect the explosion protection may only be carried out by COOPER
CROUSE-HINDS or a qualified electrician in compliance with the applicable national
rules.

Modifications to the device or changes of its design are not permitted.

9. DISPOSAL / RECYCLING

When the apparatus is disposed of, the respective national regulations on waste
disposal must be observed.  In order to facilitate the recycling of individual
components, plastic parts are provided with the identification mark of the plastic
material used.  Subject to modifications or supplement of the product range.

WARNING

To avoid the risk of fire, explosion, or electric shock, this product should be
installed, inspected, and maintained by a qualified electrician only, in
accordance with all applicable electrical codes.

All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness
thereof are not guaranteed. In accordance with Crouse-Hinds “Terms and Conditions of Sale,” and since conditions of use are outside our control, the purchaser should
determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.

Cooper Industries Inc.

IF 1604

Crouse-Hinds Division

Revision 1

PO Box 4999, Syracuse, New York 13221  •  U.S.A.

New 3/10

Copyright © 2010, Cooper Industries, Inc.

Figure 7 - Testing acc. IEC 60079-15

Summary of Contents for CHAMP IF1604

Page 1: ... inside the light fitting during operation 2 CONFORMITY WITH STANDARDS The floodlight conforms to the standards specified in the EC Declaration of Conformity It has been designed manufactured and tested according to the DIN EN ISO 9001 94 9 EC Equipment and protective systems intended for use in potentially explosive atmospheres The floodlight fulfills further requirements such as those of the EC ...

Page 2: ...a the IP protection of the whole device will be reduced The mounting directives applicable to the cable entries used shall be observed Unused holes shall be closed with a certified blanking plug in order to establish the minimum protection category In case of sealing inserts that are cut out it shall be ensured that the insert is properly adapted to the cable diameter In order to ensure the requir...

Page 3: ...to maintain the explosion category The insulation of the conductors shall reach up to the terminal The conductor itself shall not be damaged The connectible min and max conductor cross sections shall be observed see technical data All screws and or nuts of the supply terminals also of those remaining vacant shall be tightened down 4 Position the ballast cover back in place and fasten with three 3 ...

Page 4: ...cover gasket seal with a clean damp cloth If this is not sufficient use a mild soap or a liquid cleaner such as Collinite NCP or Duco 7 Do not use an abrasive strong alkaline or acid cleaner Damage may result 7 1 TEST FOR RESTRICTED BREATHING TO IEC 60079 15 33 7 1 This test is to be carried out Installation Lamp change During scheduled maintenance Check the lamp holder for damage The lamp must be...

Reviews: