2.2  Operation Characteristic Curve

2.4 Cooling and Heating Data Sheet in Rated Frequency

Model 

Rated cooling 

condition(°C) (DB/WB)

Pressure of gas pipe 

connecting indoor and 

outdoor unit 

Inlet and outlet pipe 
temperature of heat 

exchanger

Fan speed of 

indoor unit

Outdoor fan 
mode (rpm)

Indoor 

Outdoor 

P (MPa) 

T1 (°C) 

T2 (°C) 

Super High

09K

27/19

35/24

0.9~1.1

12 to 14

75 to 37

880

12K

880

18k

800

24k

800

Compressor Speed(rps)

Compressor Speed(rps)

Cooling

Heating

Current(A)

Current(A)

0

1

2

3

4

5

6

7

8

9

10

0

20

40

60

80

100

120

 WB19

°C

0

1

2

3

4

5

6

7

8

0

20

40

60

80

100

120

Condition

Indoor:DB 27°C 

Indoor air flow: Super High

Pipe length:5m

Voltage:230V

Condition

Indoor:DB 20°C

Indoor air flow: Super High

Pipe length:5m

Voltage:230V

2.3 Capacity Variation Ratio According to Temperature

50

60

70

80

90

100

110

120

130

32 33 34 35 36 37 38 39 40 41 42 43 44 45 46

Capacity ratio(%)

Outdoor temp. (°C)

Capacity ratio(%)

Heating

Cooling

-20

-15

-10

-5

0

5

10

110

120

130

100

90
80
70
60
50
40

Outdoor temp.(°C) 

Condition

Indoor:DB27°C WB19°C

Indoor air flow: 

High

Pipe length:5m

Condition

Indoor:DB20°C

Indoor air flow: 

High

Pipe length:5m

Model 

Rated cooling 

condition(°C) (DB/WB)

Pressure of gas pipe 

connecting indoor and 

outdoor unit 

Inlet and outlet pipe 
temperature of heat 

exchanger

Fan speed of 

indoor unit

Outdoor fan 
mode (rpm)

Indoor 

Outdoor 

P (MPa) 

T1 (°C) 

T2 (°C) 

Super High

09K

20/-

7/6

2.2~2.4

70 to 35

2 to 4

880

12K

880

18k

800

24k

800

T1: Inlet and outlet pipe temperature of evaporator;      
T2: Inlet and outlet pipe temperature of condenser;
P:  Pressure of air pipe connecting indoor and outdoor units.

NOTES : 
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U  bent.(Thermistor themometer) 
(2) Connecting piping condition : 5m

Summary of Contents for CH-S09FTXN-E2wf

Page 1: ...MODELS CH S09FTXN E2wf CH S12FTXN E2wf CH S18FTXN E2wf CH S24FTXN E2wf SERVICE MANUAL Nordic EVO II Series Designed by Cooper Hunter International Corporation Oregon USA www cooperandhunter com EN...

Page 2: ...rol Operation 16 7 Installation Manual 18 7 1 Notices for Installation 18 7 2 Installation Dimension Diagram 20 7 3 Installation Indoor Unit 21 7 4 Installation Outdoor Unit 24 7 5 Check after install...

Page 3: ...site after installation Make sure no foreign objects are left in the unit Always ensure effective grounding for the unit Incorrect handling could result inpersonal injury or death Incorrect handling...

Page 4: ...ht kg 11 5 11 5 Parameter Unit Value Value Outdoor Unit Outdoor Unit Model Compressor Trademark panasonic SANYO Compressor Model 5SS072ZJA21 C 1RZ110H1AE Compressor Oil FV50S or equivalent FV50BX Comp...

Page 5: ...ked Layers 7 7 Net Weight kg 14 16 5 Gross Weight kg 17 20 Parameter Unit Value Value Outdoor Unit Outdoor Unit Model Compressor Trademark SANYO SANYO Compressor Model C 6RZ146H1AG C 6RZ146H1AG Compre...

Page 6: ...ng to Temperature 50 60 70 80 90 100 110 120 130 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 Capacity ratio Outdoor temp C Capacity ratio Heating Cooling 20 15 10 5 0 5 10 110 120 130 100 90 80 70 60...

Page 7: ...f 792 279 195 CH S12FTXN E2wf 792 279 195 CH S18FTXN E2wf 972 302 224 CH S24FTXN E2wf 1081 327 248 CH S09FTXN E2wf CH S12FTXN E2wf CH S18FTXN E2wf 3 2 Outdoor Unit Unit mm Model CH S09FTXN E2wf CH S12...

Page 8: ...Compressor Refrigerant pipe diameter Liquid 1 4 6 mm Gas 3 8 9 52mm 9 12K 1 2 12mm 18K 5 8 16mm 24K 5 Schematic Diagram 5 1 Electrical Wiring Symbol OG WH YE RD YEGN BN BU BK VT Color symbol ORANGE W...

Page 9: ...3 12 Function and Control Function and Control 6 Function and Control 6 1 Remote Control Operations Health button Wi button I feel button I feel Wi fi There is no this function for some remote control...

Page 10: ...rom the aircon when press this button Default WIFI open on remote control WIFI button for air conditioner WIFI link Note Health button Note Note Note Note Turn on the back cover of the remote control...

Page 11: ...will run in few minutes before turn off when turn off in heating or indoor temperature above environment temperature 3 Sensor malfunction If the environment sensor or pipe sensor AD is above or equal...

Page 12: ...4 Select a location which is out of reach for children 5 The location should be ableto withstand the weight of indoor unit and won t increase noise and vibration 6 The appliance must be installed 2 5m...

Page 13: ...f the plastic expansion particle is loose please drill another fixing hole nearb Step 3 Open piping hole 1 Choose the position of piping hole according to the direction of outlet pipe The position of...

Page 14: ...e clip 4 Put wiring cover back and then tighten the screw 5 Close the panel Note All wires of indoor unit and outdoor unit should be connected by a professional If the length of power connection wire...

Page 15: ...ew on the right handle of outdoor unit and then remove the handle 2 Remove the screw cap of valve and aim the pipe joint at the bell mouth of pipe 3 Pretightening the union nut with hand 4 Tighten the...

Page 16: ...wing requirement after finishing installation Items to be checked Possible malfunction Has the unit been installed firmly The unit may drop shake or emit noise Have you done the refrigerant leakage te...

Page 17: ...to the diameter of liquid pipe See the following sheet Additional refrigerant charging amount for R22 R407C R410A and R134a Diameter of connection pipe Outdoor unit throttle Liquid pipe mm Gas pipe mm...

Page 18: ...01 1 15 fan motor clamp board S22020002 S22020002 1 16 fan motor S16800001 S16800001 1 17 fan motor clamp board S22020001 S22020001 1 18 drain pipe S1301000101 S1301000101 1 19 step motor S17000001 S1...

Page 19: ...10620007 1 16 fan motor clamp board S22020004 1 17 fan motor S16800003 1 18 fan motor clamp board S22020007 1 19 connction pipe pressed plate S22020005 1 20 motor stand S22020006 1 21 drain pipe S1301...

Page 20: ...ame S10620017 1 16 fan motor clamp board S22020008 1 17 fan motor S16800008 1 18 connction pipe pressed plate S22020005 1 19 drain pipe S1301000104 1 20 step motor S17000003 1 21 crank S61200002 1 22...

Page 21: ...9 S12620010 1 16 discharge pipe S12610015 S12610014 1 17 noise absorption sponge inside S61410020 1 18 noise absorption sponge outside S61410019 S61410024 1 19 big handle apricot grey S22210001 S22210...

Page 22: ...S3380000209 1 17 right side panel apricot grey S10600004P S10600004P 1 18 big handle apricot grey S22210002 S22210002 1 19 valve cover S21420007 S21420007 1 20 valve support subassembly apricot grey...

Page 23: ...s below see the process below see the process below see the process below see the process below see the process below see the process below see the process below see the process below see the process...

Page 24: ...cause of poor radiating 1 Check the voltage of power supply 2 Check the system see the process below see the process below 1 the wiring terminal between the mainboard and wifi module loosened or poorl...

Page 25: ...45 44 Troubleshooting Troubleshooting...

Page 26: ...2 11 1 Cold pasma zero wire connector 2 Power supply zero wire connector 3 PG fan contral connector 4 Cold pasma fire wire connector 5 PG fan feedback connector 6 Auto key 7 Vertical swing connector 8...

Page 27: ...del Insert the jumper cap tightly Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Replace the mainboard with the same model End Yes Yes Yes Yes Yes No No No No No 2 IDU A...

Page 28: ...nated Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Is the motor started up No Replace PG motor Replace the mainboard with the same model End Reinstall the blade and mo...

Page 29: ...inal between temperature sensor and controller is loosened or poorly contacted yes yes yes yes Insert the temperature sensor tightly no no no no Eliminate the malfunction Check whether the temperature...

Page 30: ...ording to the service manual Noted the detection method of the coil of the eletric expansion valve there is five pieces of the coil of the eletric expansion valve the resistance of one of them the lef...

Page 31: ...expansion valve 6 Compressor start failure protection L1 Main checking points If the connection wire of the compressor is connected properly Flow chart If the stop duration of the compressor is suffic...

Page 32: ...itable Flow chart 8 ODU Charging malfunction U1 Main checking points If the mainboard is broken If the wiring of the induction is connected well and if the induction is broken Flow chart Energize the...

Page 33: ...it Refrigerant is leaking Discharged air temperature during cooling is higher than normal discharged wind temperature Discharged air temperature during heating is lower than normal discharged wind tem...

Page 34: ...ormal phenomenon Abnormal sound will disappear after a few minutes When turn on or turn off the unit there s abnormal sound due to flow of refrigerant inside airconditioner Water running sound can be...

Page 35: ...08 42 24 128 78 6 542 114 2 2409 29 853 66 7 113 37 43 23 186 79 6 3315 115 2 1816 28 799 98 8 107 96 44 22 286 80 6 1288 116 2 1242 27 750 18 9 102 85 45 21 425 81 5 9336 117 2 0686 26 703 92 10 98 0...

Page 36: ...shaft on both sides of the panel to make it separate from the groove Remove the panel 3 Remove guide louver Remove axial sleeve of guide louver Procedure Note 5 Remove the filter 4 Remove electric box...

Page 37: ...at the joint of the evaporator and rear case B Adjust slightly the pipe on the evaporator to separate the pipe with the evaporator C Remove the evaporator to separate the evaporator with rear case ass...

Page 38: ...3 Remove protective grille Remove the screws fixing protective grille and then remove the protective grille Procedure 4 Remove axial flow blad Remove the nut fixing the blade and then remove the axial...

Page 39: ...iring terminals Then lift the electric box to remove it Right side plate Electric box assy Screw Left side plate Note Procedure 10 Remove motor and motor support Remove tapping screws fixing the motor...

Page 40: ...valve assy When unsoldering the spot weld wrap the 4 way valve with wet cloth completely to avoid damaging the valve due to high temperature 4 way valve assy Isolation sheet Screw Note Procedure 14 Re...

Page 41: ...co onstantly y w w wo o ork king g to o im m mpro o ov v ve th heir pro o od d du u ucts so o th he inf f fo o orm m matio on in th his m m manu ual is su u ub b bj jject to o ch hang ge w with h ho...

Reviews: