Appendix 2
The installation explanation of automatic filled-water
1 When automatic filled-water valve is installed,the arrowhead orientation of inlet water must
accord with the orientation of valve ;
2 Automatic filled-water has been adjusted in advance to 1.5bar
3 If readjust the pressure of inlet water,please operate as follows
* open the screw cap
C
* If reduce the pressure of water supply,
p
l
ease unscrew the pressure to adjust the
screw(B)
* If increese the pressure of waer supply,please screw down the pressure to adjust the screw (B)
4 When the system need fill water at first,wrest the handle(A) of filled-water.Then the handle(A)
can return(close) when the system is full of water.
5 Automatic filled-water Valve need clean in a periodic time and then you must close the tap,
unscrew the plug(D),remove the inside filter net.
Please assemble them again after cleaning.
NOTICE
There are two connections for water pressure meter in the central section of
automatic filled-water,where the water pressure meter can be connected directly
and display the set pressure.The screw cap(C) must be tweaked after adjusting
the filled-water pressure.
B
C
1/4'
D
A
1/2'