Revised: 02/12/2015
2/12/2015
10
NOTE: AIR INTAKE RESTRICTOR PLATE MUST BE REMOVED
FOR FLUE LENGTHS OF MORE THAN 1 METRE.
INBUILT & FREESTANDING Rear Vent Flue Installation
1. Determine the exact location for the heater.
2.
Mark the exact location for the wall penetration
a.
Determine that you will not be cutting through any vertical wall studs.
b.
Check that the location of the wall-mounted terminal conforms to the
requirements of AS/NZS5601.1 – Location of a Flue Terminal.
3.
Cut 2 holes 70mm in diameter at 160mm centres holes to be side by side in the
horizontal.
4.
Use the back of the cowl as a template for fixing holes.
5.
Fit flex flue to spigots on the rear of the cowl using provided hose clamps and seal with
silicone (high temp).
NOTE- it may be necessary to trim the flue depending on wall thickness.
6. Attach the back of the cowl to the wall. Silicone around outside.
I
NSTALLATION - GAS PRESSURE TO GAS VALVE
NAT 1.1 KPA
Only to be carried out by a Coonara authorised technician!
1.
Unpack flue kit and log set. (Packed inside with heater).
2.
Carefully remove the cardboard carton surrounding the heater, then remove the heater from
the pallet.
3.
Position heater, locate and connect flue pipes to unit. Connect gas to the flexible connection
line and check pressure coming in. Minimum pressure required – NAT GAS = 1.1. High
and low settings on gas valve are factory set and should be correct. (Refer to page 4 for
pressure settings.) Check these settings are correct. Do not adjust gas valve. Call the factory
if settings are incorrect.
4.
Remove door frame by undoing 2 screws on left hand side of the door & 2 screws on right
hand side of the door.
5.
Start by pressing
power button
on the thermostat and then follow the instructions in the
thermostat manual supplied. Heater will not light for approx 1 minute. Once the firebox gets
warm it will then go to higher temp. Switch off using
power button
on the thermostat. This
may have to be done 2 – 3 times, until unit is purged.
6.
Once heater is working, unpack log set and place in firebox, making sure you do not move
the sensor or sparker when placing the logs.
7.
Re assemble heater in reverse order.
8.
INBUILT HEATER
- Fascia Panel hooks on to the unit at the top. One screw secures the
fascia at centre bottom under door.
9.
FREESTANDING HEATER
- Fascia Panel hooks on to the unit at the top. Two screws
secure the fascia at the bottom left and right hand side of fascia.
INSTRUCT CUSTOMER OF CORRECT OPERATING PROCEDURE
.
Summary of Contents for Royal Classic
Page 12: ...Revised 02 12 2015 2 12 2015 12...
Page 13: ...Revised 02 12 2015 2 12 2015 13...
Page 14: ...Revised 02 12 2015 2 12 2015 14 INBUILT INSTALLATION...
Page 16: ...Revised 02 12 2015 2 12 2015 16...
Page 17: ...Revised 02 12 2015 2 12 2015 17...
Page 18: ...Revised 02 12 2015 2 12 2015 18...
Page 21: ...Revised 02 12 2015 2 12 2015 21 WIRING DIAGRAM FOR THERMOSTAT Sit Gear Tray PRESSURE SWITCH...
Page 24: ...Revised 02 12 2015 2 12 2015 24 STEP 2 STEP 3 STEP 4...
Page 25: ...Revised 02 12 2015 2 12 2015 25 STEP 5 STEP 6 LOG SET FRONT VIEW...