ATTENTION TO RIGGERS
•
Insert 2" nominal pipe through holes in the base rail as shown in the figure below for slings.
•
Holes in base rail are centered around the unit center of gravity.
•
Use wooden pallet or spreader bar when rigging, to prevent the slings from damaging the unit.
•
Rollers may be used to move the unit on the roof or ground.
CAUTION:
All panels should be in place when rigging.
RIGGING INSTRUCTIONS
MODELS: PT036 - PT360
5
SERVICE CLEARANCE
MODEL
DIMENSIONS
NUMBER
A
B
C
D
PT036
85
105
85
150
PT048
85
105
85
150
PT060
85
105
85
150
PT075
90
105
90
200
PT090
90
105
90
200
PT100
90
105
90
200
PT120
90
105
90
200
NOTE
: All dimensions are in cm.
A : Clearance dimension from condenser coil
B : Clearance dimension from compressor, control box, blower, evaporator coil & filter
C : Clearance dimension from condenser coil & filter
D : Clearance dimension over the condenser fan
MODEL
DIMENSIONS
NUMBER
A
B
C
D
E
PT180
120
120
115
250
90
PT215
120
120
115
250
90
PT240
120
120
115
250
90
PT300
120
120
115
250
90
PT360
120
120
115
250
90
A : Clearance dimension from condenser coil
B : Clearance dimension from compressor, control box & evaporator coil
C : Clearance dimension from condenser coil & blower
D : Clearance dimension over the condenser fan
E : Clearance dimension from filter access panel
MODELS: PT036 - PT120
MODELS: PT180 - PT360
NOTE
: Only two condenser fans for models PT180 - PT240.
SPREADER BAR
NOMINAL PIPE THRU UNIT FOR SLINGS TO AVOID BASE DAMAGE.
END
PROPER CLEARANCE TO BE
PROVIDED.
COMPRESSOR
LIFT
LIFT
2. PIPE DIA 2" FOR PT090 TO PT360 MODELS
1 .PIPE DIA 1 1/2" FOR PT036 TO PT075 MODELS
Note: