9
M100 FireGard
TM
Chain & Crank
02/11
TERMINAL CONNECTIONS
Disconnect power supply before servicing.
TB1
L1 L2
Input power 115VAC
*
, Not Supervised
See
Note. 4
TB2
1 (
+
) 2
(
-
)
3 4
*
5 6 7 8 9
Input 24VDC/VAC
Use Power Limited source
only
Not Supervised
*Note. 4
Alarm Dry Contact (N/C)
Not Supervised
*Note 1
Alarm door close warning
24VDC, total 1A
Common, Not Supervised
*Note 2
Brake release status
(Dry contact)
24VAC/VDC, 2A Max.
Resistive load, Common,
Not Supervised
*Note 3
Close
button
Dry contact (N/C)
*Note
:
1. Terminal 3&4
Building fire alarm panel (FACP) needs to provide dry contact (N/C) connection with minimum capacity of 24VDC and 0.5 amp.
Terminal 4
When connecting more than one wire/connector to the terminal, must use enclosed Part # CDA-FH600-WHF02. See page 13 for
illustration.
2. Terminal 6&7
This connection provides 24VDC, 1A power with 18AWG wire for maximum of 20 ft. Upon alarm signal, this connection can be
used to provide power for warning devices. The warning power is provided for less than a minute. The wiring connections are
enclosed within conduit or equivalently protected against mechanical injury.
3. Terminal 8&9
These terminal connections will provide the status of this release device. When release device is in the standby mode, connection is
open (N/O). When release device have been activated or released, connection would be in closed (N/C) state.
4.
See connection chart for power inputs. A regulated, power limited UL1481 Power Supply must be used for this terminal.
WARNING