background image

6

HMD IO&M

B51242-002

Tolerance

Center Distance

Maximum Gap

Up thru 12”

1/16”

12” up through 48

1/8”

Over 48”

1/4”

NOTICE! Premature or frequent belt failures can 

be caused by improper belt tension, or misaligned 

sheaves. Abnormally high belt tension or drive mis-

alignment will cause excessive bearing loads and 

may result in failure of the fan and/or motor bearings. 

Abnormally low belt tension will cause squealing on 

start-up, excessive belt flutter, slippage, and overheat

-

ed sheaves.

1.  V-belt drives must be checked on a regular basis for 

wear, tension, alignment, and dirt accumulation.

2. 

Check the tension by measuring the deflection in the 

belt as shown here.

3.  Check the alignment by using a straight edge across 

both sheaves. The drawings below show where to 

measure the allowable gap for the drive alignment 

tolerance. All contact points (indicated by WXYZ) are 

to have a gap less than the tolerance shown in the 

table. When the pulleys are not the same width, the 

allowable gap must be adjusted by half of the differ

-

ence in width.

Snow Accumulation

Clear snow away from roof mounted units. Keep the 

snow clear of the intake and access doors.

Motors

Motor maintenance is generally limited to cleaning and 

lubrication (where applicable). Cleaning should be limited 

to exterior surfaces only. Removing dust and grease build-

up on the motor assures proper motor cooling. 

Motors supplied with grease fittings should be greased 

in accordance with the manufacturer’s recommendations. 

Greasing motors is only intended when fittings are provid

-

ed. Many motors are permanently lubricated, requiring no 

additional lubrication.

NOTICE! Do not allow water or solvents to enter the 

motor or bearings. Motors and bearings should never 

be sprayed with steam, water or solvents.

3.  With all access panels in place, the fan running and 

discharging 70ºF (21ºC) air, connect a U-Tube ma-

nometer to the outer sensing probes and measure 

the static pressure across the burner. The proper 

static pressure should be (check 

CFM / Static Pres-

sure chart

 on page tk). If needed, evenly adjust the 

baffles, keeping the burner centered in the opening 

until the required pressure is obtained. The pressure 

drop was set at the factory and may not need adjust-

ment. When required pressure is obtained, be sure 

to reconnect the outer sensing probes. This process 

may need to be repeated until the proper pressure is 

achieved. This adjustment will change the air quanti-

ty delivered by the unit and therefore the air quantity 

delivered should be rechecked. Refer to the 

Blower 

Start-Up

 section.

•  To increase static pressure decrease the opening.

•  To decrease static pressure increase the opening.

4.  Monitor the unit’s actual temperature rise by placing 

a thermocouple in the unit’s inlet and a second in the 

discharge, three duct diameters downstream of the 

burner. Send the unit to maximum flame by chang

-

ing the rotation of the motor pack from left to right. 

Use a screw driver on top of modular gas valve. 

While monitoring the unit’s temperature rise, set the 

maximum firing rate by adjusting the regulator until 

the designed temperature rise is achieved. After set-

ting the maximum firing rate, reconnect the wire to 

the amplifier. Do not set the burner maximum firing 

rate based on gas pressure. It should be set based 

on the unit’s designed temperature rise shown on 

the  label.  Setting  the  maximum  firing  rate  during 

mild weather conditions may cause the high limit to 

trip out during extreme conditions requiring manual 

resetting. Gas trains are equipped with a combined 

regulator valve. Clockwise rotation increases the 

temperature rise; counterclockwise rotation de-

creases the temperature rise. The minimum setting 

for the maximum firing rate may be higher than re

-

quired. This is acceptable, the burner will modulate 

as needed. To convert from Natural Gas to LP or 

vice versa follow the instructions associated with the 

high fire gas valve.

5.  Set the operating temperature.

Maintenance - All year

V-Belt Drives

NOTICE! Do not pry belts on or off 

the sheave. Loosen belt tension 

until belts can be removed by 

simply  lifting  the  belts  off 

the sheaves. When replac-

ing V-belts on multiple 

groove drives, all belts 

should be changed to 

provide uniform drive 

loading. Do not install 

new belts on worn 

sheaves. If the sheaves have grooves worn in them, 

they must be replaced before new belts are installed.

1 foot

1/4 inch

Summary of Contents for HMD

Page 1: ...n powered fan the impeller can rotate which is referred to as windmill ing Windmilling will cause hazardous conditions due to unexpected rotation of components Impellers should be blocked in position...

Page 2: ...tandard for Repair Garages ANSI NFPA 88B and with CAN CSA B149 1 Natural Cas and Propane Installation Codes NOTICE Adequate building relief shall be provid ed so as to not over pressurize the building...

Page 3: ...th local codes or in the absence of local codes in ac cordance with the National Fuel Gas Code ANSI 2223 1 NFPA 54 or the CAN CSA B149 1 Natural Cas and Propane Installation Code NOTICE When a duct wo...

Page 4: ...he Reference section for location of optional components Heating Inlet Air Sensor Typical setting 60 70 F Building Freeze Protection Typical setting 45 F Dirty Filter Gauge Typical setting Settings va...

Page 5: ...ing probe high 14 Pressure sensing probe low 15 Temperature controller 16 Thermostat to blower 17 Safety Shut off valve 18 Pressure gauge 19 Gas valve 20 Modulating gas valve 21 Pressure gauge 22 Safe...

Page 6: ...entered in the opening until the required pressure is obtained The pressure drop was set at the factory and may not need adjust ment When required pressure is obtained be sure to reconnect the outer s...

Page 7: ...re installed they can be checked by holding up to a light source If light cannot pass through the filter it should be replaced When reinstalling filters be sure to install them with the airflow in the...

Page 8: ...inal 2 Is there 120 VAC between terminal blocks 1 5 Is there 120 VAC between across A1 A2 on supply contactor 1 Replace fan belt if broken 2 Repair or replace motor or capacitor if needed 3 Repair mot...

Page 9: ...n the wrong direction If the blower is rotating in the wrong direction the unit will move some air but will not perform as designed Is the motor voltage correct Is the motor horse power too low Shorte...

Page 10: ...as needed 2 Install automatic belt tensioner if possible Adjust the drives as needed Consult factory Measure the unit s air volume cfm and compare it with its rated air volume If the measured air vol...

Page 11: ...volume If the measured air volume is wrong adjust the fan s RPM by changing adjusting the drive The most accurate way to measure the air volume is by using a Pitot traverse method downstream of the b...

Page 12: ...Clean or replace filters as needed Are the sheave aligned Is the wheel unbalanced Are the filters dirty clogged Are the bearings worn or do they need lubrication Yes Yes Yes Yes Yes 1 Replace or tigh...

Page 13: ...CFM Static Pressure chart on page 8 If needed evenly adjust the baffles keeping the burner centered in the opening until the required pressure is obtained The pressure drop was set at the factory and...

Page 14: ...until the required pressure is obtained The pressure drop was set at the factory and may not need adjustment When required pressure is obtained be sure to reconnect the outer sensing probes This proc...

Page 15: ...15 B51242 002 HMD IO M Service Contacts Dealer Installation Contractor Service Contractor Date of Installation Name Address Phone Name Address Phone Name Address Phone...

Page 16: ...to the specific model and serial numbers of your fan Upon receipt by Loren Cook Company of your written complaint you will be notified within thirty 30 days of our receipt of your complaint in writing...

Reviews: