background image

8

HMD IO&M

B51242-002

No

No

No

No

No

Is the proper power 

supply at the main 

disconnect?

1. Compare the supplied voltage, hertz, and phase with the motor’s 

nameplate information.

2. Make sure disconnect switch is on.

Replace 480-120v transformer #A

1. Make sure supply switch is on.

1. Correct supply fan overload if tripped. Check for proper voltage, amps 

and RPMs.

2. Check optional exhaust fan interlocks

Is there 120 VAC 

between terminals X2 & 

X1 on transformer #A?

Is there 120 VAC between 

terminal block #2 &  

circuit breaker terminal 2?

Is there 120 VAC 

between terminal blocks 

1 & 5?

Is there 120 VAC 

between across A1 & 

A2 on supply contactor?

1. Replace fan belt, if broken.

2. Repair or replace motor or capacitor if needed.

3. Repair motor fuse if needed.

4. Repair or replace one or more of the motor 

wiring legs, if needed.

At this time the supply contactor 

should pull in, passing power to the 

supply motor & blower should start.

Yes

Yes

Yes

Yes

Yes

1. Install the optional damper limit switch, if not installed. If holding, wait 

for actuator to fully open or adjust the limit switch.

2. Repair or replace fan relay if not energizing. Check for loose 

connection.

Troubleshooting

Blower does not operate

Refer to the control panel parts list when troubleshooting.

Summary of Contents for HMD

Page 1: ...n powered fan the impeller can rotate which is referred to as windmill ing Windmilling will cause hazardous conditions due to unexpected rotation of components Impellers should be blocked in position...

Page 2: ...tandard for Repair Garages ANSI NFPA 88B and with CAN CSA B149 1 Natural Cas and Propane Installation Codes NOTICE Adequate building relief shall be provid ed so as to not over pressurize the building...

Page 3: ...th local codes or in the absence of local codes in ac cordance with the National Fuel Gas Code ANSI 2223 1 NFPA 54 or the CAN CSA B149 1 Natural Cas and Propane Installation Code NOTICE When a duct wo...

Page 4: ...he Reference section for location of optional components Heating Inlet Air Sensor Typical setting 60 70 F Building Freeze Protection Typical setting 45 F Dirty Filter Gauge Typical setting Settings va...

Page 5: ...ing probe high 14 Pressure sensing probe low 15 Temperature controller 16 Thermostat to blower 17 Safety Shut off valve 18 Pressure gauge 19 Gas valve 20 Modulating gas valve 21 Pressure gauge 22 Safe...

Page 6: ...entered in the opening until the required pressure is obtained The pressure drop was set at the factory and may not need adjust ment When required pressure is obtained be sure to reconnect the outer s...

Page 7: ...re installed they can be checked by holding up to a light source If light cannot pass through the filter it should be replaced When reinstalling filters be sure to install them with the airflow in the...

Page 8: ...inal 2 Is there 120 VAC between terminal blocks 1 5 Is there 120 VAC between across A1 A2 on supply contactor 1 Replace fan belt if broken 2 Repair or replace motor or capacitor if needed 3 Repair mot...

Page 9: ...n the wrong direction If the blower is rotating in the wrong direction the unit will move some air but will not perform as designed Is the motor voltage correct Is the motor horse power too low Shorte...

Page 10: ...as needed 2 Install automatic belt tensioner if possible Adjust the drives as needed Consult factory Measure the unit s air volume cfm and compare it with its rated air volume If the measured air vol...

Page 11: ...volume If the measured air volume is wrong adjust the fan s RPM by changing adjusting the drive The most accurate way to measure the air volume is by using a Pitot traverse method downstream of the b...

Page 12: ...Clean or replace filters as needed Are the sheave aligned Is the wheel unbalanced Are the filters dirty clogged Are the bearings worn or do they need lubrication Yes Yes Yes Yes Yes 1 Replace or tigh...

Page 13: ...CFM Static Pressure chart on page 8 If needed evenly adjust the baffles keeping the burner centered in the opening until the required pressure is obtained The pressure drop was set at the factory and...

Page 14: ...until the required pressure is obtained The pressure drop was set at the factory and may not need adjustment When required pressure is obtained be sure to reconnect the outer sensing probes This proc...

Page 15: ...15 B51242 002 HMD IO M Service Contacts Dealer Installation Contractor Service Contractor Date of Installation Name Address Phone Name Address Phone Name Address Phone...

Page 16: ...to the specific model and serial numbers of your fan Upon receipt by Loren Cook Company of your written complaint you will be notified within thirty 30 days of our receipt of your complaint in writing...

Reviews: