MV3DB Series DB Units
3. System Design
(07/06)
ALSPA MV3000e Dynamic Braking Units
Page 3-9
Figure 3-6 EMC considerations
AC Line
Reactor
EMC
Filter
Contactor
Fuses
SEG REG ATIO N
y
Control & power wiring
must cross at 90
o
and be
separated by
≥
300 mm
(12 in).
y
Power input & output
wiring must be separated
by
≥
300 mm (12 in).
Braking resistor in
metal box
Thermostat wiring
300 mm
(12 in)
minimum
300 mm
(12 in)
minimum
300 mm
(12 in)
minimum
External
Supply
Cabinet
Boundary
Mains
Supply
Cable outside cabinet to be
screened and to be glanded
at both ends
Isolator
2
Cable inside cabinet must
comply with segregation rules
To reduce induced noise, the
two wires connecting the
braking resistor to the drive
should always be run together.