4 Modbus/TCP
Ethernet Option Board /
700.002 735 AE01
4-3
The following table shows a MODBUS query that changes the engine's rotation direction by entering “1” for
control-word bit 1 value. This example uses the 'Write Coil' MODBUS function. Note that Control word is
application specific and use of bits may vary depending on it.
Query:
0x00, 0x00, 0x00, 0x00, 0x00, 0x06, 0x01, 0x05, 0x00, 0x01, 0xFF, 0x00
Data
Purpose
0x00
Transaction ID
0x00
Transaction ID
0x00
Protocol ID
0x00
Protocol ID
0x00
Length
0x06
Length
0x01
Unit identifier
0x05
Write coil
0x00
Reference number
0x01
Reference number
0xFF
Data
0x00
Padding
Table 4-4: Writing a Single Control Word Bit
4.3.2
0017 – 00018 Counters (Read Only)
The frequency converter's operation day trip counter and energy trip counter can be reset by entering “1” as
the value of the coil in request. When the value “1” is entered, the device resets the counter. However, the
device does not change the Coil value after reset but maintains the “0” mode.
Address
Function
Purpose
0017
Clear OpDay
Clears OpDay counter
0018
Clear MWh
Clears MWh counter
Table 4-5: Counters
The following table represents a MODBUS query that resets both counters simultaneously. This example
applies the 'Force Multiple Coils' function. The reference number indicates the address after which the
amount of data defined by the 'Bit Count' is written. This data is the last block in the MODBUS/TCP message.
Data
Purpose
0x00
Transaction ID
0x00
Transaction ID
0x00
Protocol ID
0x00
Protocol ID
0x00
Length
0x08
Length
0x01
Unit identifier
0x0F
Force multiple coils
0x00
Reference number
0x10
Reference number
0x00
Bit count
0x02
Bit count
0x01
Byte Count
0x03
Data
Table 4-6: Force Multiple Coils Query
Summary of Contents for 700.002 735
Page 1: ...Ethernet Option Board LV7000 Order No 700 002 735 Issue 06 08 AE01 Operating Manual ...
Page 8: ...Contents Ethernet Option Board 700 002 735 AE01 ...
Page 10: ...1 Introduction 1 2 Ethernet Option Board 700 002 735 AE01 ...
Page 14: ...2 Ethernet Board Technical Data 2 4 Ethernet Option Board 700 002 735 AE01 ...
Page 20: ...3 Installation 3 6 Ethernet Option Board 700 002 735 AE01 ...
Page 30: ...4 Modbus TCP 4 10 Ethernet Option Board 700 002 735 AE01 ...
Page 32: ...5 Start up Test 5 2 Ethernet Option Board 700 002 735 AE01 ...
Page 34: ...6 Error Codes and Errors 6 2 Ethernet Option Board 700 002 735 AE01 ...
Page 37: ......