Controlsoft SOLO CS-AC-3210 Installation Instructions Manual Download Page 6

6

SOLO - Programming

REMOVE USERS

To remove one or more users, present the Master Card to a reader until the controller 

beeps once and then three times. 

Press and hold button S1 and the display will show the user number  

0 0 1

Repeatedly press button S1 to step up through the user numbers, or hold it down to 

scroll faster. Release the button when the required user number is displayed.
Press button S2, the controller beeps and the number changes to  

- - -

. The 

selected user has now been removed from the memory 

The SOLO has 2 timers for door control as described below: 

DOOR RELEASE TIME

This is the duration that the door remains unlocked following presentation of a valid 

card.  This duration can be adjusted from 1 seconds (default) up to 9 seconds in 

intervals of 1 second.

DOOR OPEN ALARM DURATION

If a door contact is fitted and the door is left open for too long, the controller can 

generate an alarm condition and activate the siren.  This duration can be adjusted 

from 30 seconds (default) up to 4 minutes 30 seconds in intervals of 30 seconds.

Program Timers

Press and release button S1. The display will show  

  t 1

.  This indicates the default 

Door Release Time of 1 second. 
Press and release button S1 again to increment the setting to 

  t 2

 (2 seconds).  

Continue to the maximum setting of 

  t 9

 (9 seconds). 

NOTE: The display 

  t -

 indicates a special operating mode for interfacing to other 

equipment, whereby the door relay is pulsed for 150ms.

When the desired time is shown on the display, either progress to the Door Open 

Alarm Duration (see below), or end programming mode by leaving the controller until 

it beeps 3 times and the display clears.

To program the Door Open Alarm Duration, press and release button S2 and the 
display changes to 

  A 1

. This indicates the default duration of 30 seconds.

Press button S2 to increment the setting to 

  A 2

 (1 minute). 

Continue to press S2 up to the maximum setting of 

  A 9

 (4 minutes 30 seconds).

When the desired Door Open Alarm Duration is shown on the display, end 

programming mode by leaving the controller until it beeps 3 times and the display 

clears.

Important!

 A door open alarm can only be generated if a door contact is fitted to the 

system.

Summary of Contents for SOLO CS-AC-3210

Page 1: ...s Power 12V to 24V ac or dc Current 100mA 12V with 1 reader head Readers One or two compatible reader heads CS AC 3211 Mullion CS AC 3212 Vandal Resistant or CS AC 3213 Panel Mount Inputs Normally Ope...

Page 2: ...oller for 1 reader head To use two reader heads remove the jumper and fit it across both pins as shown NOTE If this jumper is not in the correct position the system may experience seemingly random or...

Page 3: ...blocks 1 and 8 The Fire Alarm Panel must provide voltage free normally open contacts Step 5 Connect Outputs The SOLO has two relay outputs one for the electric door lock and the other for an alarm si...

Page 4: ...eakglass applies power to the door strike to ensure that the door is released in an emergency ALWAYS fit a MOV across the coil of the door strike to prevent Back EMF from damaging the SOLO Siren Use t...

Page 5: ...buttons and wait 30 seconds for the display to clear then try again ENROL USERS Present the Master Card to a reader for approximately 5 seconds until the controller beeps once and then three times Thi...

Page 6: ...lt up to 4 minutes 30 seconds in intervals of 30 seconds Program Timers Press and release button S1 The display will show t 1 This indicates the default Door Release Time of 1 second Press and release...

Page 7: ...0 0 1 Repeatedly press S1 until required user number shown Press and hold S2 beep Door Release Time Door Open Alarm Duration Press S1 t 1 1 second Default Press S1 t 2 2 seconds etc up to Press S1 t 9...

Page 8: ...e feel free to photocopy this page to record further users SOLO User List Controlsoft UK 44 0 1451 844896 support controlsoft com controlsoft uk support Information on all our products can be found on...