10) Engine Safety Configuration
Heading
Default
Range
Units
Your Settings
Press and Temp Units
English
English / Metric
Sender Check Bypass
0:10
0:05
– 1:00
Min:Sec
Fuel Level Sender
S-W
S-W / VDO
Fuel Level Check
Off
Off / Always / Run
Low Fuel Prealarm
20
0 - 100
%
Low Fuel Alarm
1
0 - 100
%
Fuel Alarm Delay
0:01
0:01
– 1:40
Sec
Oil Pressure Sender
S-W
S-W / VDO
Oil Pressure Check
Run
Off / Always / Run
Low Oil Press Prealarm
15
0 - 100
PSI
Low Oil Press alarm
10
0 - 100
PSI
Oil Press Alarm Delay
5
0:01
– 1:40
Sec
Temperature Sender
S-W
S-W / VDO
Temperature Check
Run
Off / Always / Run
Low Temp Prealarm
0
0 - 300
Deg F
Low Temp Alarm
0
0 - 300
Deg F
High Temp Prealarm
220
150 - 300
Deg F
High Temp Alarm
230
150 - 300
Deg F
Temp Alarm Delay
0:05
0:01
– 1:40
Min:Sec
Battery Volts Check
Off
Off / Always / Run
Lo Battery Prealarm
10.0
0.0
– 40.0
Volts
Hi Battery Prealarm
15.0
0.0
– 40.0
Volts
Battery V Trim
5
0-10
100mV
Over Speed Check
Run
Off / Always / Run
Over Speed Alarm
4200
650 - 5000
RPM
Over Speed Alarm Delay
0:05
0:01
– 1:40
Min:Sec
Notes
1) Off / Always / Run
– Describes when the parameter will be monitored for alarm conditions. Run refers to when
the engine is running. Off disables the alarm conditions. Always enables the alarm constantly regardless of engine
state.
2) Alarm Delay
– The time period, after Sender Check Bypass, that the parameter must be on the alarm condition
before the alarm becomes latched.