background image

ISO 9001

Label

Description

Function

Cable type

Max wire 

length

L1

24Vac/dc

Power supply

AWG 16 ( min 

1mm

2

 - max 

1,5mm

2

)

75m

Ln

0V

Y

0-10Vdc

Modulating 

control input

AWG 20 ( min 

0,5mm

2

 - max 

1,5mm

2

)

200m

M

0V (common)

Y1

Open

Floating control 

input

AWG 20 ( min 

0,5mm

2

 - max 

1,5mm

2

)

200m

Y2

Close

V+

16Vdc

Voltage output 

max 25mA

AWG 20 ( min 

0,5mm

2

 - max 

1,5mm

2

)

200m

M

0V (common)

U

2-10Vdc

Feedback 

output signal

AWG 20 ( min 

0,5mm

2

 - max 

1,5mm

2

)

200m

M

0V (common)

Etichetta

Descrizione

Funzione

Tipo cavo

Lunghezza 

massima del 

cavo 

L1

24Vac/dc

Alim.

AWG 16 ( min 

1mm

2

 - max 

1,5mm

2

)

75m

Ln

0V

Y

0-10Vdc

Ingresso 

comando 

modulante

AWG 20 ( min 

0,5mm

2

 - max 

1,5mm

2

)

200m

M

0V (comune)

Y1

Apertura

Ingresso 

comando flottante

AWG 20 ( min 

0,5mm

2

 - max 

1,5mm

2

)

200m

Y2

Chiusura

V+

16Vdc

tensione massima 

in uscita 25mA

AWG 20 ( min 

0,5mm

2

 - max 

1,5mm

2

)

200m

M

0V (comune)

U

2-10Vdc

uscita segnale di 

feedback

AWG 20 ( min 

0,5mm

2

 - max 

1,5mm

2

)

200m

M

0V (comune)

MORSETTIERA / TERMINAL BLOCK

L1 / Ln

0 V

24Vac/dc

N4170-04

U

Y M Y1 Y2

Corrispondenza morsetti rispetto alle altre linee di prodotto ser-

vocomandi Controlli.  

Terminals correspondence with respect to other Controlli actu-

ators models.

N.B.

: Non esercitare una pressione eccessiva quando si inse-

risce la morsettiera per evitare che la flessione del PCB possa 

danneggiare i componenti elettronici sulla scheda.

Note

: To avoid damages to electronic components caused by 

the PCB bending, do not press too much while fixing the termi

-

nal block.

K1    K2  KC1

K1    K2  KC1

End point position

End point position

DMVE

RELE' DI CHIUSURA

RELE' DI APERTURA

K3    K4  KC2

Posizione di fine corsa

Posizione di fine corsa

K3    K4  KC2

OPENING RELAY

CLOSING RELAY

DMVE

DMVE:

 Caratteristiche elettriche / Electrical rating: 24V AC/DC, 4A

PASSACAVI / CABLE GLAND

Utilizzare passacavi modello PG13,5 (non forniti).

Use cable gland PG13,5 model (not supplied).
VERSIONE IP65 fornito con pressacavo PG13,5 per cavi con 

Ø variabile tra 6 e 12 mm.

IP65 MODEL suitable with PG13,5 cable gland for cables with 

Ø variable between 6 and 12 mm

.

COLLEGAMENTI DI TERRA / GROUND CONNECTION

Collegare il terminale di terra nell’apposita vite etichettata con il 

simbolo della messa a terra come indicato in figura. 

Connect the ground terminal to the proper screw labelled with 

the ground symbol as shown in the following picture.

1 Emissione / 1

st

 

Issue 

rev. 

e 10/17 

  2      DIM196

Summary of Contents for MVE5 Series

Page 1: ...il info controlli eu Web www controlli eu ISTRUZIONI DI MONTAGGIO MOUNTING INSTRUCTIONS Servocomandi per valvole Valve actuators MVE5xx MVE5xx 65 1 Emissione 1st Issue rev e 10 17 1 DIM196 N4170 17 T fluido fluid 120 C T fluido fluid MAX 120 C T fluido fluid 120 C 1 2 3 4 INSTALLAZIONE INSTALLATION ...

Page 2: ...olli Terminals correspondence with respect to other Controlli actu ators models N B Non esercitare una pressione eccessiva quando si inse risce la morsettiera per evitare che la flessione del PCB possa danneggiare i componenti elettronici sulla scheda Note To avoid damages to electronic components caused by the PCB bending do not press too much while fixing the termi nal block K1 K2 KC1 K1 K2 KC1 ...

Page 3: ... power other devices using not isolated double half wave rectifier power supply Comando flottante a 3 punti Connessione source 24Vac 0V Controllore APRI CHIUDI L1 Y1 Y2 MVE Ln COMANDO COMANDO Controllore MVE 24Vac 24Vdc 0V Comando modulante 0 10Vdc L1 Ln Y M Controller 3 point floating control sink connection 0V Y2 Ln MVE Y1 OPEN 24Vac 24Vdc L1 CLOSE 3 point floating control source connection 24Va...

Page 4: ... interruttore in ON in presenza di scontro inatteso o extra corsa il servocomando non aggiornerà la corsa U 2V U 10V U feedback U 10V U 2V Y1 U feedback DIP switch OFF ON 1 Direct Action Reverse Action 2 Modulating Control MOD Input between Y and M 3 point floating INC Y1 open extend Y2 close retract connected L1 or Ln if powered in Vac if powered in Vdc connected necessarily to Ln 3 Selection of ...

Page 5: ... corsa dopo 10s Range errato Perdita del linkage o valvola non adatta corsa superiore a 60mm Spegnere Il servocomando e ripetere la fase di calibrazione 3 ROSSO LAMPEGGIANTE VELOCE Scontro inatteso entro il range di corsa calcolato IN FUNZIONAMENTO NORMALE Il servocomando verifica la condizione di stallo per 5 volte Al termine dei tentativi segnala anomalia Il servocomando apprende la nuova corsa ...

Page 6: ...ower up again 2 RED LED quick blinking GREEN ON Stroke longer than 60mm Calibration first installation The actuator exits the 60mm stroke range and it moves toward the new stroke limit signalling an anomaly The actuator pushes pulls 2 times against the new stroke limit then it goes back to the initial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate...

Reviews: