background image

Controlli S.p.A.

16010 Sant’Olcese (GE)

Tel. 010 73 06 1

Fax. 010 73 06 870/871

www.controlli.eu

APPLICATION AND USE

MVE2xx-65 is a flexible electro-mechanical actuator for the control of 

two and three way globe valves in:

• 

heating and cooling systems

• 

Air Handling Units

• 

district heating plants

• 

industrial temperature control systems.

MVE2xx-65 can be controlled either by a proportional (modulating) 

signal or by an increase/decrease (Floating) signal.

It is easy to mount and connect the actuator. Direct mounting is pos

-

sible to any CONTROLLI flanged valve. Linkage kits are available for 

CONTROLLI threaded valves as well as for valves of other manufac

-

turers (table page 3).

The actuator has a fine resolution (500 steps on the full stroke range) 

for exacting fluid control and it is able to self-calibrate on a different 

stroke without the need of any user action (this function is DIP switch 

selectable on the field).

MVE2xx-65 has intelligent behaviour and alarm functionality in case 

of unexpected operation, feedback of alarms to the user is provided 

by LEDs (GREEN and RED) on the control board.

N.B.: Do not use the actuator if not coupled with its relating valve.

MVE2xx-65 is suitable for harsh environment requiring IP65 protection 

degree.

 

OPERATION

The  actuator  translates  the  control  signal  (modulating  or  3  point 

floating) from the controller into a valve position. A modern brushless 

DC motor in the actuator drive a gear train and a worm gear – screw 

IP65 Globe Valves Actuators

MVE2xx-65

jack  mechanism  convert  the  motor  revolutions  into  accurate  and 

repeatable linear movements.

Control Signal

MVE2xx-65 can be controlled by one of 2 main control types.

• 

3 point floating;

• 

modulating (or proportional) signal with field selectable range 

(e.g., 0-10Vdc, 2-10Vdc, 0-5/2-6Vdc, 5-10/6-10Vdc and 4-20mA).

Manual Override

There is a manual operation handle on the actuator. When it is low

-

ered (manual override ON), the power supply to the motor power 

stage circuitry is cut and the motor stops. The actuator can be op

-

erated manually and the valve positioned accordingly. The manual 

override lever latches in position until it is raised again, then board 

and motor will be powered again. At the end of this operation the 

actuator moves to initial position (on the basis of DIP n. 1 setting) then 

it follows the control signal. When the manual override is engaged 

the GREEN and the RED LED are ON.

Manual operation handle can also be used to modify any DIP switch 

setting or as re-set function after any alarm occurrence. The actua

-

tor is supplied with the manual override lowered (ON).

t is not necessary to remove power supply to modify DIP switch set

-

ting, but, in this case, take care of 230Vac voltage.

Feedback position

The actuator utilizes a 2-10V position feedback (look at DIP n. 1 set

-

ting).

Calibration

The actuator has both auto and manual stroke calibration, DIP n. 7. 

In factory delivery the auto stroke calibration is enabled – manual 

calibration is not necessary unless maintenance is required on the 

valve or certain alarm functions are desired.

1

st

 Issue rev. c

06/2020

DBL561e

Page 1

MODEL

FORCE 

[N]

POWER SUPPLY

DESCRIPTION

MVE204-65 

400

230Vac±10%

long yoke, modulating/

floating control, IP65

MVE206-65 

600

MVE210-65 

1000

MVE215-65

1500

MVE222-65

2200

MVE204S-65 

400

230Vac±10%

short yoke, modulating/

floating control, IP65

MVE206S-65 

600

MVE210S-65 

1000

MVE215S-65

1500

MVE222S-65

2200

 The device contains electrical and electronic components and is not allowed to be disposed 

of as household refuse. All locally valid regulations and requirements must be observed.

Summary of Contents for MVE2-65 Series

Page 1: ...odulating or proportional signal with field selectable range e g 0 10Vdc 2 10Vdc 0 5 2 6Vdc 5 10 6 10Vdc and 4 20mA Manual Override There is a manual operation handle on the actuator When it is low er...

Page 2: ...s for valves with stroke from 25 to 60 mm Increase decrease 60 s Stroke 5 60 mm limited to 30 mm for MVE2xxS 65 Force 400 N 600 N 1000 N 1500 N 2200 N Duty cycle max 50 60 minutes Analogue input Y M v...

Page 3: ...olli valves except for 2 3TGB F PN16 VSXT09PBP VSXT10PBP only with MVE204S 65 2 3TGB F PN16 Controlli valves with threaded M40 connections except for VSB VMB VSB F VMB F PN16 with AG51 VSB VMB VSB F V...

Page 4: ...1 F M N Neutral Modulating Control o 10 Vcc Modulating Control 0 10Vcc 230Vac Controller Command Command MVE M Y F N Neutral Note To avoid damages to electronic components caused by the PCB bending do...

Page 5: ...DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc w...

Page 6: ...nitial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and p...

Page 7: ...tor arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is...

Reviews: