background image

ISO 9001

10. Loosen the universal mounting clamp (making sure not to 

move the damper shaft) and rotate the actuator approximately 
5° in the direction which would open the damper.

11. Tighten the universal mounting clamp to the shaft, ensuring 

that it is in the correct mounting position.

12. Manually rotate the actuator to align with universal bracket.
13. Pivot the universal bracket into place and secure both sides.
14. Tighten all fasteners. Tighten the two nuts on the clamp using 

a 7/16” spanner or socket and apply 8.2 to 10.8 Nm of torque.

15. Check that the universal mounting clamp (or AM-709) pointer 

mounting position is at 5°.

1

st 

Issue 

   09/13 

  4      DBL153e

Correct universal clamp pointer 
mounting position (after 5° Pre-
tensioning) 

Jackshaft Installation (MA40-704X, MF40-7043, MS40-
7043Series)

The MA40-704X, MF40-7043 and MS40-7043 series actuators 
are designed for use with jackshafts up to 16mm in diameter. 
In most applications, the actuator may be mounted in the same 
manner as a standard damper shaft application. If the jackshaft 
diameter is larger than 16mm in diameter, the optional AM-710 
universal clamp must be used.

Adjusting an Auxiliary Switch (where fi tted)

The MA40-704X-G01, MF40-7043-G01 and MS40-7043-G01
actuators include one built-in SPDT auxiliary switch which can 
be used for interfacing or signalling (e.g., for fan start-up). The 
switch is adjustable between 0° and 95° of rotation (0 to 1 scale). 
To make an adjustment:
1.  The actuator must be in its normal (spring return) position.
2. Use a 

fl

 at screw driver to rotate the switch pointer until it is at 

the desired switch position on the 0 to 1 scale.

Rotation Limitation

The Stop Block is used in conjunction with the tab on the universal
clamp or the AM 709 position indicator. In order to function pro-
perly, the clamp or indicator must be mounted correctly.
The Stop Block is used in applications where a damper has a 
designed rotation that is less than 90°, for example with a 45° 
or 60° rotating damper.
1.  Determine the amount of damper rotation required. The 

actuator stop block provides limited rotation from 40° to 95.

2.  Loosen the screw securing the stop block to the actuator.

Note: The actuator is shipped with the Stop Block mounted 
to the ‘L’ side. If the damper application requires the ‘R’ side 
face the installer, simply remove the Stop Block and screw 
and move it to the new location.

Adjusting Stop Block for Limited Rotation

WIRING DIAGRAMS

Class 2 control and power lead wiring must be routed separa-
tely from line voltage wiring and any other non-class 2 circuits. 
Line voltage, auxiliary switch and auxiliary switch leads must be 
connected to a Class 1 circuit.
WARNING - these are spring return acutators. Keep clear of all 
moving parts when power is removed. Only switch off power if 
spring return is required.

Model

Series

Max cable lenght (m)

14 AWG

16 AWG 18 AWG

24Vac

MA40-7043-G00

335

213

134

MA40-7043-G01

24Vac

MF40-7043-G00

183

122

76

MF40-7043-G01

24Vac

MS40-7043-G00

213

131

82

MS40-7043-G01

24Vac

MA40-7041-G00

11,278

7,163

4,511

MA40-7041-G01

TWO POSITION CONTROL - 230V

TWO POSITION CONTROL - 24V

Reviews: