background image

ISO 9001

3.  Test for adequate shaft length by sliding the actuator over 

the shaft. The shaft should extend at least 3mm through 
the clamp. Long shafts should be at least 90mm, in which 
case the clamp should be 

fi

 tted on the installer’s side of 

the actuator, and short shafts should be at least 20mm, in 
which case the clamp should be 

fi

 tted to the damper side 

of the actuator.

Note: All actuators are shipped with a standard universal 
mounting clamp installed. For damper shafts larger than 
16mm in diameter, the AM-710 universal mounting clamp 
is required (order separately). The AM-710 clamp accom-
modates round shaft sizes up to 19mm in diameter

4.  On the basis of the shaft lenght proceed as follows.

Long Damper Shaft Mounting

Clockwise motor drive

Counterclockwise spring return

Counterclockwise motor drive

Clockwise spring return

• 

Determine the best orientation for the universal mounting 
clamp on the back of the actuator. The best orientation pro-
vides the easiest access to the two nuts on the V-clamp.

• 

Engage the clamp to the actuator as close as possible to 
the determined orientation, then lock the clamp in place 
using the remaining retainer clip. 

• 

Place position indicator on the actuator and secure with the

• 

retainer clip. Ensure that the position indicator is at the be-
fore Pre-tensioning position (see following illustration).

• 

Position the damper at its normal (spring return) position 
and check that it is fully closed or completely open.

Position Indication and Pre-tensioning

5. Slide the actuator over the shaft and verify that the position 

indication pointer on the universal mounting clamp is in the 
normal spring return position.

• 

Secure the universal mounting clamp to the actuator using 
the retaining clip.

• 

Position the damper at its normal (spring return) position 
and check that it is fully closed or completely open.

• 

Continue from Step 5.

Short Damper Shaft Mounting

1

st 

Issue 

   09/13 

  3      DBL153e

Correct universal clamp poin-
ter mounting position if ac-
tuator is in normal spring 
return position (before Pre-
tensioning)

6.  Tighten the universal mounting clamp, 

fi

 nger tight only.

7. Align the universal bracket at the base of the actuator and 

drill mounting holes. Bend the bracket as needed to reach the 
duct.

8.  Place a No.8 self-tapping screw in one side of the universal 

bracket and mount it the duct at the base of the actuator. Do 
not tighten the screw.

9.  Pivot the universal bracket away from the actuator.

Central line

With clamps loosened, ro-
tate approx. 5° away from 
vertical, tighten clamps, then 
return to vertical

.

1,6 ÷ 4,8 mm